When
, DAR, or PI is activated, pressing the TEST button starts the test. The LCD displays the measurement, along
with a "countdown" timer showing the time remaining in the test. The test automatically stops when the duration end time is
reached and the result is displayed.
Successive presses on the
For
For PI and DAR:
Use the following table as a guide for interpreting the results of a DAR or PI test:
DAR
DAR < 1.25
1.25 ≤ DAR < 1.6
1.6 ≤ DAR
Press the TEST button to return to voltage measurement.
TEST
20
1.800.561.8187
DAR
M
button display intermediate values. These include
:
Programmed time, voltage, and current at the end of the measurement
T1 time and the voltage, current, and insulation resistance at that time
T2 time and the voltage, current, and insulation resistance at that time.
PI
PI < 2
2 ≤ PI < 4
4 ≤ PI
www.
M
Condition of insulation
Poor or even dangerous
Good
Excellent