Execution example of the BACnet monitoring function

This section shows an execution example of the BACnet monitoring function which monitors the PresentValue property value
of an AnalogInput object (instance number: 10) in another BACnet device (instance number of a device: 3) from a BACnet
module.
Assignment of an access block for BACnet monitoring
Assign an access block for BACnet monitoring in [Settings]  [BACnetMonitor] as follows.
Item
DeviceInstanceNo
ObjectID
PropertyID
ArrayIndex
Interval (Sec)
BufferMemoryAddress
For the assignment method, refer to the operating procedure from 1 to 4 described in the following section.
Page 140 How to use the BACnet monitoring function
1 FUNCTIONS
144
1.6 BACnet Monitoring Function
Description
3
ObjectType: AnalogInput, Instance number: 10
PresentValue
 (No settings)
60
500