Mitsubishi Electric MELSEC iQ-R User Manual page 248

Bacnet module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

Message log
LimitedBroadcast Sock getaddrinfo
255.255.255.255 XX Error
LimitedBroadcast Sock setsockopt
SO_BROADCAST Error
LimitedBroadcast Sock setsockopt
SO_REUSEADDR Error
LimitedBroadcast Sock Bind Error
Unicast recvfrom Error
SendUdp socket not opened
UnicastSendSub UniCastSocket is
INVALID_SOCKET
UnicastSendSub sendto error
destination=XXXX
CDataLink_IPV4::Unicast Buffer size over
XXXX limit=YYYY
UnconfirmedRequest IllegalHeader
Header=XX
WebListenThread Socket Create Error
WebListenThread bind Error
3 TROUBLESHOOTING
246
3.5 Message Log List
Log level
Message detail
Major error
The IP address of the specified limited
broadcast was not set for the BACnet
module.
Major error
The IP address of the specified limited
broadcast was not set for the BACnet
module.
Major error
The IP address of the specified limited
broadcast was not set for the BACnet
module.
Major error
The IP address of the specified limited
broadcast was not set for the BACnet
module.
Major error
Packet receiving failed.
Major error
A packet could not be sent because the IP
address setting failed.
Major error
A packet could not be sent because the IP
address setting failed.
Major error
An attempt was made to send a packet, but
it failed.
Major error
An attempt was made to send a packet, but
the packet size exceeded the upper limit.
Major error
The sent packet is invalid.
Major error
A socket for a configuration function (web
browser) could not be created.
Major error
A socket for a configuration function (web
browser) could not be registered.
Corrective action
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, initialize or
replace the BACnet module.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, initialize or
replace the BACnet module.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, initialize or
replace the BACnet module.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, initialize or
replace the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, initialize
or replace the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, initialize
or replace the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, initialize
or replace the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, replace
the BACnet module.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, replace
the BACnet module.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective action, replace
the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, initialize
or replace the BACnet module.
• Review the setting of the IP address.
• Turn the power OFF and ON, or reset the
CPU module.
• If the same message appears even after
taking the above corrective actions, initialize
or replace the BACnet module.