Mitsubishi Electric MELSEC iQ-R User Manual page 117

Bacnet module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

4.
Set the following properties.
PropertyI
Property
D
126
BufferSize
132
LogDeviceObjectProperty
133
LogEnable(Enable)
134
LogInterval
142
StartTime
143
StopTime
144
StopWhenFull
197
Logging_Type
• To check log records
Click the [Show] button on the LogBuffer property of a TrendLog object to display log records.
• To check log records using another BACnet device
Send a ReadRange service in which a LogBuffer property is specified.
Description
Specify the number of records to be sampled.
Specify a logging target object and its property.
To start logging, select True.
To stop logging, select False.
Specify a logging cycle. (Unit: 10 milliseconds)
Specify a time to start logging.
Specify a time to stop logging.
Select whether to stop logging or continue logging by
overwriting old records when the number of records specified to
a BufferSize property is sampled by a LogBuffer property.
Select "Polled" when logging data with the cycle specified to the
LogInterval property.
Select "COV" when logging data at the timing of sending a COV
from a logging target object.
Remarks
To sample records every one minute for two
days, specify '2880'.
To perform logging every one minute, specify
'6000'.
When a time is not specified, data logging is
started immediately after the
LogEnable(Enable) property becomes True.
When a time is not specified, the timings to
stop logging are as follows:
• The LogEnable(Enable) property became
False.
• The number of logs exceeded the capacity
of the LogBuffer when the StopWhenFull
property is True.
Only ANSI/ASHRAE 2010 is supported.
1 FUNCTIONS
1.1 BACnet Object Function