Csv File For The Cov Interaction Function - Mitsubishi Electric MELSEC iQ-R User Manual

Bacnet module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

CSV file for the COV interaction function

If a value outside the range is set, the data in the corresponding row will not be added and overwritten to a BACnet module.
Column
Column
No.
comment
1
DeviceInstanceNo
2
ObjectType
3
ObjectInstanceNo
*1
4
RWordAddress
5
SubscribeCOVEnabl
e
6
ProcessID
7
Confirm
8
LifeTime
*1 The RWordAddress is handled as a word address by default.
If other than "RWordAddress" is entered to the column comment, the buffer memory address will be handled as a byte address.
CSV file for the Event interaction function
If a value outside the range is set, the data in the corresponding row will not be added and overwritten to a BACnet module.
Column
Column
No.
comment
1
DeviceInstanceNo
2
ObjectType
3
ObjectInstanceNo
*1
4
RWordAddress
*1 The RWordAddress is handled as a word address by default.
If other than "RWordAddress" is entered to the column comment, the buffer memory address will be handled as a byte address.
Description of data row
Instance number of a COV notification send
source device
Object type number of a COV notification send
source object
Instance number of a COV notification send
source object
Buffer memory address of an access block for
COV interaction
Enable SubscribeCOV.
ProcessID
Confirmed/Unconfirmed
Cycle to read values (minutes)
Description of data row
Instance number of an Event notification send
source device
Object type number of an Event notification
send source object
Instance number of an Event notification send
source object
Buffer memory address of an access block for
Event interaction
Value to be set
Range: 0 to 4194303
To receive COV notifications which are sent from a BACnet module,
set the instance number of the BACnet module.
For the instance number of a BACnet module, refer to the following
section.
Page 198 Setting an instance number and a BACnet standard
Range: 0 to 1023
Range: 0 to 4194303
0: A free space is assigned. If there is no free space, a data block is
not assigned.
Other than 0: Specify a buffer memory address in decimal. If a part of
the set buffer memory address has already been used, a data block
will not be assigned.
0: Disable
1: Enable
Range: 1 to 4294967295
0: Unconfirmed
1: Confirmed
Range: 1 to 1440
Value to be set
Range: 0 to 4194303
To receive Event notifications which are sent from a BACnet module,
set the instance number of the BACnet module.
For the instance number of a BACnet module, refer to the following
section.
(Page 198 Setting an instance number and a BACnet standard)
Range: 0 to 1023
Range: 0 to 4194303
0: A free space is assigned. If there is no free space, a data block is
not assigned.
Other than 0: Specify a buffer memory address in decimal. If a part of
the set buffer memory address has already been used, a data block
will not be assigned.
Appendix 5 CSV File Format
A
APPX
277