Mitsubishi Electric MELSEC iQ-R User Manual page 181

Bacnet module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

■ At the joining/leaving of BACnet
In the following BACnet standards, COV notifications can be sent when joining and leaving BACnet.
• ANSI/ASHRAE 2004
• IEIEJ-G-0006:2006 Addendum-a
• ANSI/ASHRAE 2010
Set the send target of COV notifications when joining/leaving BACnet to the Restart_Notification_Recipients property of a
Device object.
The following shows how to set the Restart_Notification_Recipients property of a Device object.
Operating procedure
1.
Select [BACnetObject] to open the "BACnet Objects" screen.
2.
Click the [Browse] button of "Device".
3.
Click the [Details] button in the row where "ObjectName" is "RJ71BAC96".
4.
Click the [Add] button of "Restart_Notification_Recipients".
5.
Set the send target of COVs. A send target can be set by specifying either a DeviceID or a BACnetAddress.
• How to specify a DeviceID
Enter the instance number of a send target device in the rightmost textbox.
• How to specify a BACnetAddress
Select "BACnetAddress" from the leftmost pull-down list, and specify a BACnetAddress by referring to the following section.
Page 104 How to specify a BACnetAddress
1 FUNCTIONS
1.12 Configuration Function