Stop request from a program
A BACnet module can be stopped using a program with the following procedure.
■ CheckYDevice in the BACnet detail setting is '0'
A BACnet module cannot be stopped using a program.
■ CheckYDevice in the BACnet detail setting is '1'
Operation of a BACnet
module
BACnet communication is in
operation.
BACnet leaving processing is
started.
After the module has left from
BACnet, the value of X2 is changed
to '0'.
The BACnet communication is
stopped.
X0
X1
X2
Operation in a program
1
1
1
The value of Y1 is changed to '0' to
issue a stop request.
10
0
The value of X2 is changed to '0' and
the BACnet communication is regarded
as stopped.
Y1
Remarks
1
In operation
10
0
APPX
Appendix 1 I/O Signals
A
253