4.
Check the buffer memory address.
Create a program to set a write target by referring to the format of access blocks for writing. Replace the offset +0 in the
format of access blocks for writing with the buffer memory address displayed with a configuration function. (Page 292
Format of access blocks for writing)
5.
Set the property of a write target to the access block for writing using a program, and store '1' to the CONTROL. (The
BACnet module sends a WritePropertyMultiple service. Page 136 Execution example of the write function)
For the operation of a BACnet module, refer to the following section.
Page 134 Operation of a BACnet module
6.
Select [BACnetRequest]  [Write] , and click the [Detail] button of the data bock to which the write function is executed.
7.
Check the execution result.
If an error occurred, check the row of "Status" and take corrective actions.
1 FUNCTIONS
1.5 BACnet Request Function (Write Function)
1
133