Advertisement

5.
Check the buffer memory address.
Create a program to read the monitored value by referring to the format of access blocks for BACnet monitoring. Replace the
offset +0 in the format of access blocks for BACnet monitoring with the buffer memory address displayed with a configuration
function. (Page 293 Format of access blocks for BACnet monitoring)
6.
When the CONTROL of the access block for BACnet monitoring is '1', read the monitored value from the access block
for BACnet monitoring using a program.
For the operation of a BACnet module, refer to the following section.
Page 143 Operation of a BACnet module
7.
Select [BACnetMonitor], and click the [Detail] button of "DeviceInstanceNo" to check the monitored value.
8.
Check the monitored value.
If an error occurred, check the row of "Status" and take corrective actions.