Mitsubishi Electric MELSEC iQ-R User Manual page 81

Bacnet module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

■ Pulse input
The usage of a pulse input area differs depending on the value set to "PulseDirectInput" in [Settings]  [Basic Information] 
[BACnet Detail Setting] button  "Interface". (Page 281 Interface)
• When the value is '0': The offset +3 is not used.
Bit position
Name
b15
Reset flag
b14 to b0
CTA
*1
• When the value is '1'
: The offset +2 and the offset +3 are used.
Bit position
Name
b31 to b0
PresentValue
*1 When '1' is set to "PulseDirectInput", an Event notification cannot be sent from an Accumulator object. To send an Event notification, set
'0'. (Page 184 Accumulator object)
Remarks
Pulse counter value
Remarks
32-bit unsigned integer
1 FUNCTIONS
1.1 BACnet Object Function