■ Pulse input
The usage of a pulse input area differs depending on the value set to "PulseDirectInput" in [Settings] [Basic Information]
[BACnet Detail Setting] button "Interface". (Page 281 Interface)
• When the value is '0': The offset +3 is not used.
Bit position
Name
b15
Reset flag
b14 to b0
CTA
*1
• When the value is '1'
: The offset +2 and the offset +3 are used.
Bit position
Name
b31 to b0
PresentValue
*1 When '1' is set to "PulseDirectInput", an Event notification cannot be sent from an Accumulator object. To send an Event notification, set
'0'. (Page 184 Accumulator object)
Remarks
Pulse counter value
Remarks
32-bit unsigned integer
1 FUNCTIONS
1.1 BACnet Object Function