Buffer memory format of MultiStateInput objects
The following shows the format of properties assigned to the buffer memory.
Additionally, the availability of reading from/writing to a CPU module is shown in the following table.
R: Read-only, W: Write-only, R/W: Read/Write
Offset
Name
+0
CONTROL
+1
STATUS
+2
PresentValue
+3
1 FUNCTIONS
60
1.1 BACnet Object Function
b15
OutOfService
b14 to b4
b3 to b0
Reliability
b15 to b14
b13 to b11
EventState
b10
AckedTransition
b9
b8
b7
b6
EventEnable
b5
b4
b3
StatusFlags
b2
b1
b0
b15 to b0
PresentValue
Remarks
0: False, 1: True
• When '1' is set to "OutOfServiceControl" in [Settings]  [Basic
Information]  [BACnet Detail Setting] button  "Interface",
the value of an OutOfService property is stored.
Not used
0: NoFaultDetected
1: NoSensor
2: OverRange
3: UnderRange
4: OpenLoop
5: ShortedLoop
6: NoOutput
7: UnreliableOther
8: ProcessError
9: MultiStateFault
10: ConfigurationError
Not used
0: Normal
1: Fault
2: Offnormal
3: HighLimit
4: LowLimit
5: LifeSafetyAlarm
ToOffnormal
0: False, 1: True
ToFault
0: False, 1: True
ToNormal
0: False, 1: True
Not used
ToOffnormal
0: False, 1: True
ToFault
0: False, 1: True
ToNormal
0: False, 1: True
InAlarm
0: False, 1: True
Fault
0: False, 1: True
Overridden
Always 0
OutOfService
0: False, 1: True
16-bit value
Not used
R/W
R/W
R
R/W