Specifications - Altronix AL400ULACM Installation Manual

Acm series access power with power supplies
Hide thumbs Also See for AL400ULACM:
Table of Contents

Advertisement

These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into
eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry
form "C" contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access
Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hard­
ware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe
and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger
other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
AL400ULACM
4A
AL600ULACM
6A
AL1012ULACM 10A - - - - - - - - ­
AL1024ULACM - - - - - - - - ­ 10A 8 3.5A No
Power Supply Input Options:
• a) One (1) common power input for ACM8 and lock power (factory installed).
b) Two (2) isolated power inputs (external power supply is required).
(current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled outputs.
Output Options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form "C" 5 amp rated relay outputs.
c) Any combination of the above.
• Eight (8) auxiliary power outputs (unswitched) (outputs are rated 3.5 amp).
• ACM8 board main fuse is rated at 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is triggered (form "C" contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Filtered and electronically regulated outputs (built-in power supply).
• Built-in charger for sealed lead acid or gel type batteries.
• AL400ULXB2, AL600ULXB, and AL1012ULXB (Power Supply Board) maximum charge current 0.7 amp.
AL1024ULXB2 (Power Supply Board) maximum charge current 3.6 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Thermal and short circuit protection with auto reset.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact).
• Battery fail and battery presence supervision (form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm).
- 2 -
ACM Series Configuration Reference Chart:
3A
8 3.5A Yes
3.5A
6A
8 3.5A No
3.5A
8 3.5A No
2.6A
4.2A

Specifications:

Available from A1 Security Cameras
www.a1securitycameras.com email:sales@a1securitycameras.com
Overview:
5A/250V 15A/32V
5A/250V
- - - - - - - - -
5A/250V 15A/32V
5A/250V 15A/32V
Altronix Corp.
140 58th St. Brooklyn, NY
(File # BP6714)
NYC
UL Listed for Access
California
Dept. of
State Fire
Buildings
Control System Units.
Marshal
"Signal Equipment"
Evaluated to CSA
LISTED
Standard C22.2
No.205-M1983
UL 294
ACM series