Fig. 2
Door
Wire
Strap
(from
Enclosure
to Door)
Green
Flying
Lead
CAUTION: Optional rechargeable stand-by batteries must match
the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
*When class 2 rating is required order model numbers:
AL400ULACMCB, AL600ULACMCB, AL1012ULACMCB and AL1024ULACMCB
- 6 -

Power Supply Board

CAUTION: De-energize unit prior to servicing.
For continued protection against fire hazard replace
fuse with the same type and rating.
L
G
N
unswitched
115VAC
power mains
(non power-limited)
Inputs (power-limited)
IN GND
IN GND
IN GND
IN GND
1
2
3
4
F1
F2
F3
F4
3.5A 250V
3.5A 250V
3.5A 250V
3.5A 250V
LED1
LED2
LED3
LED4
NC C NO COM
NC C NO COM
NC C NO COM
NC C NO COM
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
DC Output to devices (power-limited for AL400ULACM,
non power-limited for all other models*)
Optional Rechargeable
Stand-by Battery
Available from A1 Security Cameras
www.a1securitycameras.com email:sales@a1securitycameras.com
ON
OFF --- 24V
ON --- 12V
SW1
Battery and AC
Supervision Circuit
(power-limited)
AC DELAY
BAT FAIL
AC FAIL
IN GND
IN GND
IN GND
IN GND
5
6
7
8
F5
F6
F7
F8
O N
1
2
3
4
3.5A 250V
3.5A 250V
3.5A 250V
3.5A 250V
LED5
LED6
LED7
LED8
J3
NC C NO COM
NC C NO COM
NC C NO COM
NC C NO COM
OUTPUT 5
OUTPUT 6
OUTPUT 7
OUTPUT 8
Observe
polarity
Insulating
Barrier
Fire
TRG
Alarm
Interface
O N
1
2
3
4
MAIN
10A 250V
J2
J1
Optional Rechargeable
Stand-by Battery