Power Supply Board
Terminal Legend Function/Description
L, N
Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
AL400ULACM - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8 board (power-limited).
AL600ULACM - 12VDC/24VDC @ 6 amp to ACM8 board (non power-limited).
+ DC –
AL1012ULACM - 12VDC @ 10 amp to ACM8 board (non power-limited).
AL1024ULACM - 24VDC @ 10 amp to ACM8 board (non power-limited).
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
AC FAIL
energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is
NC, C, NO
reported within 1 minute of event. To delay reporting of up to 6 hrs. cut "AC delay" jumper and
reset power to unit.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when
DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 min­
BAT FAIL
utes. Battery reconnection is reported within 1 minute.
NC, C, NO
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACM),
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACM).
Stand-by battery connections. AL400ULXB2, AL600ULXB and AL1012ULXB
+ BAT –
(Power Supply Board) maximum charge current is 0.7 amp. AL1024ULXB2
(Power Supply Board) maximum charge current is 3.6 amp.
ACM8 Access Power Controller
Terminal Legend
Function/Description
– Power +
12VDC or 24VDC input from power supply board.
These terminals can be connected to a separate power-limited UL Listed power supply to
– Control +
provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).
TRIGGER
From normally open and/or open collector sink trigger inputs
INPUT 1 - INPUT 8
(request to exit buttons, exit pir's, etc.).
IN, GND
12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
OUTPUT 1 -
Fail-Secure [NO positive (+) & COM Negative (-)],
OUTPUT 8
Auxiliary output [C positive (+) & COM Negative (-)]
NC, C, NO, COM
(When using AC power supplies polarity need not be observed),
NC, C, NO become form "C" 5 amp 24VAC/VDC rated dry outputs when fuses are removed.
Contacts shown in a non-triggered state.
FACP INTERFACE
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
T, + INPUT –
normally closed from an FACP output circuit (Fig. 4 through 8, pg. 8).
FACP INTERFACE
Form "C" relay contact rated @ 1 amp 28VDC for alarm reporting.
NC, C, NO
(This output has not been evaluated by UL).
ACM series
Terminal Identification Tables: