Typical Application Diagram; Led Diagnostics - Altronix AL400ULACM Installation Manual

Acm series access power with power supplies
Hide thumbs Also See for AL400ULACM:
Table of Contents

Advertisement

Fig. 1
Access Control Panel
C
Output
NO
Relay
NC
F1
LED1
Mag.
Lock
NC C NO COM
NC C NO COM
OUTPUT 1
Electric
Strike
Electromagnetic
Door Holders
Power Supply Board
LED
Red (DC)
Green (AC)
ON
ON
ON
OFF
OFF
ON
OFF
OFF
Red (Bat)
Battery Status
ON
Normal operating condition.
OFF
Battery fail/low battery.
ACM8 Access Power Controller
LED
ON
LED 1 - LED 8 (Red) Output relay(s) energized.
Trg (Green)
FACP input triggered (alarm condition).
ACM series

Typical Application Diagram:

Normally Open (N.O.)
Door Releasing
Device
Keypad
IN GND
IN GND
IN GND
IN GND
IN GND
IN GND
1
2
3
4
5
F2
F3
F4
F5
LED2
LED3
LED4
LED5
NC C NO COM
NC C NO COM
NC C NO COM
OUTPUT 2
OUTPUT 3
OUTPUT 4
UL Listed
Power Supply
For this application
corresponding
fuse F8 must be
removed.

LED Diagnostics:

Power Supply Status
Normal operating condition.
Loss of AC. Stand-by battery supplying power.
No DC output. Short circuit or thermal overload condition.
No DC output.
Available from A1 Security Cameras
www.a1securitycameras.com email:sales@a1securitycameras.com
Fig. 1a
Intact = Dry Input
Cut = Wet Input
TRG
TRG
IN GND
IN GND
6
7
8
F6
F7
F8
O N
O N
1
2
3
4
LED6
LED7
LED8
J3
NC C NO COM
NC C NO COM
NC C NO COM
OUTPUT 5
OUTPUT 6
OUTPUT 7
OUTPUT 8
MAG.
LOCK
J3
Intact = DC Input
Cut = AC Input
NC C NO COM
OUTPUT 8
OFF
Output relay(s) de-energized.
FACP normal (non-alarm condition).
FACP
(Fire Alarm
Control
Panel)
FACP Dry
Form "C" Output
SW1-SW8
1
2
3
4
FACP Interface
Disabled
MAIN
10A 250V
Enabled
J2
J1
AC or DC
AC or DC
Power
Power
Supply
Supply
(req'd.)
(optional)
Fig. 1d
Intact = One P/S Input
Cut = Dual P/S Input
J2 J1
Fig. 1b
Fig. 1c
- 5 ­

Advertisement

Table of Contents
loading

This manual is also suitable for:

Al1012ulacmAl1024ulacmAl600ulacm

Table of Contents