Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trig- ger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. ACMCB220 Series Configuration Reference Chart: Altronix...
Connect the negative (–) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO]. ACMCB220 series - 3 -...
Note: AL400XB2V, AL600XB220, AL1012XB220 (Power Supply Board) maximum charge current is 0.7 amp. AL1024XB220 (Power Supply Board) maximum charge current is 3.6 amp. Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary. - 4 - ACMCB220 series...
Battery Status Normal operating condition. Battery fail/low battery. ACM8CB Access Power Controller LED 1 - LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). ACMCB220 series - 5 -...
DC Output to devices Optional Rechargeable Optional Rechargeable Stand-by Battery Stand-by Battery Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting. - 6 - ACMCB220 series...
Page 7
FACP output circuit (Fig. 4 through 8, pg. 8). FACP INTERFACE Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting. NC, C, NO (This output has not been evaluated by UL). ACMCB220 series - 7 -...
Fig. 7 Normally Closed - Non-Latching FACP Fig. 8 Normally Closed - Latching FACP trigger input trigger input: with reset: (This output has not been evaluated by UL) N.C. RESET SWITCH N.C. DRY TRIGGER INPUT N.C. TRIGGER JUMPER JUMPER INPUT - 8 - ACMCB220 series...
Page 9
36AH. You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement. To determine actual battery size please round line [J] to the nearest larger standard battery size. ACMCB220 series - 9 -...
Page 12
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. MEMBER IIACMCB220 series G01N - 12 - ACMCB220 series...