Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm discon- nect feature is individually selectable for any or all of the eight (8) outputs. ACMCB Series Configuration Reference Chart: Altronix Model Number AL400ULACMCB 1.9 amp 3.5A / 250V UL File # BP6714 UL Listed for Access Control AL600ULACMCB 1.9 amp...
Hook-up Diagrams (pg. 8) 2. Set output voltage: AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board. AL1012ULACMCB is 12VDC and AL1024ULACMCB is 24VDC (Output Voltage and Stand-by Specification Charts below).
4. Connect AC (Fig. 2, pg. 6): Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power limited wiring separate from non-power limited wiring (115VAC 60Hz Input, Battery Wires).
(Output Voltage and Stand-by Specification Charts, pg. 3). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [- BAT +] to insure that there is no break in the battery connection wires.
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating . Green Replace fuse cover before energizing. Lead ALTRONIX CORP. BKLYN, N.Y. 11220 MADE IN USA Green BAT FAIL AC FAIL...
Page 7
Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground. - DC + AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited). AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited).
Hook-up Diagrams: Fig. 4 Polarity reversal input from FACP signaling circuit Fig. 3 Optional hook-up using two (2) isolated output (polarity is referenced in alarm condition): power supply inputs: CUT JUMPERS J1 AND J2 JUMPER J3 FACP OUTPUT EOL ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8CB POWER) FROM FACP...
Page 9
AL1024ULACMCB Battery Size Calculation Worksheet. A. AL1024ULACMCB internal current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A B. Load current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A C.
Page 12
Notes: Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIACMCB series L06G MEMBER - 12 - ACMCBseries...