Hookup Diagrams - Altronix AL400ULACM Installation Manual

Acm series access power with power supplies
Hide thumbs Also See for AL400ULACM:
Table of Contents

Advertisement

Fig. 3 Optional hook-up using two (2) isolated
power supply inputs:
CUT JUMPERS
J1 AND J2
J2
J1
Fig. 5 Normally Open - Non-Latching FACP
trigger input:
TRG
Fig. 7 Normally Closed - Non-Latching FACP
trigger input:
TRG
- 8 -
Hook-Up Diagrams:
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(ACM8 POWER)
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(LOCK POWER)
N.O. TRIGGER
INPUT
N.C. DRY
TRIGGER
INPUT
JUMPER
Available from A1 Security Cameras
www.a1securitycameras.com email:sales@a1securitycameras.com
Fig. 4 Polarity reversal input from FACP signaling circuit
output (polarity is referenced in alarm condition):
CUT
JUMPER
TRG
Fig. 6 Normally Open FACP Latching trigger input
with reset:
(This output has not been evaluated by UL)
TRG
Fig. 8 Normally Closed - Latching FACP trigger input
with reset:
(This output has not been evaluated by UL)
TRG
FACP
OUTPUT EOL
FROM FACP
--
OUTPUT
+
CIRCUIT
N.O.
TRIGGER
INPUT
N.C. RESET
SWITCH
JUMPER
N.C. RESET
SWITCH
N.C. TRIGGER
JUMPER
INPUT
ACM series

Advertisement

Table of Contents
loading

This manual is also suitable for:

Al1012ulacmAl1024ulacmAl600ulacm

Table of Contents