Overview: Altronix ACMJ Series units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.
Input: Outputs (cont’d): • Power input 115VAC, 60Hz • Alarm output relay indicates that FACP input is (see ACMJ Series Power Supply Configuration triggered (form “C” contact rated @ 1A 28VDC, Reference Chart, pg. 2). not evaluated by UL). • ACM8 Power Input Options: •...
Page 4
When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed (Fig. 1d, pg. 6). Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control Systems and accessories. - 4 - ACMJ Series...
FACP output circuit (Fig. 4 through 8, pgs. 8-9). FACP INTERFACE Form “C” relay contact rated @ 1A 28VDC for alarm reporting. NC, C, NO (This output has not been evaluated by UL). ACMJ Series - 5 -...
Battery Status Normal operating condition. Battery fail/low battery. ACM8 Access Power Controller LED 1 - LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). - 6 - ACMJ Series...
Page 7
CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. *When Class 2 rating is required order model numbers: AL400ULACMCBJ, AL600ULACMCBJ, AL1012ULACMCBJ and AL1024ULACMCBJ ACMJ Series - 7 -...
Page 9
Fig. 7 Normally Closed: Non-Latching FACP trigger input: FACP N.C. DRY TRIGGER INPUT JUMPER Fig. 8 Normally Closed: Latching FACP trigger input with reset: (This output has not been evaluated by UL) FACP N.C. RESET SWITCH N.C. TRIGGER JUMPER INPUT ACMJ Series - 9 -...
Page 10
36AH. You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement. To determine actual battery size please round line [J] to the nearest larger standard battery size. - 10 - ACMJ Series...
14.5” (368.3mm) Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. MEMBER IIACMJ Series E28S...