Altronix LINQ8ACM Installation And Programming Manual

Dual input network access power controllers

Advertisement

Quick Links

Dual Input Network
Access Power Controllers
Installation and Programming Manual
Models include:
LINQ8ACM
- Network Access Power Controller
- Eight (8) Fused Outputs
LINQ8ACMCB
- Network Access Power Controller
- Eight (8) PTC Outputs
DOC#: LINQ8ACM Rev. 100219
Please be sure to visit
altronix.com for
latest firmware and
installation instructions
More than just power.
TM

Advertisement

Table of Contents
loading

Summary of Contents for Altronix LINQ8ACM

  • Page 1 Dual Input Network Access Power Controllers Installation and Programming Manual Models include: LINQ8ACM - Network Access Power Controller - Eight (8) Fused Outputs LINQ8ACMCB - Network Access Power Controller - Eight (8) PTC Outputs More than just power. DOC#: LINQ8ACM Rev. 100219...
  • Page 2: Specifications

    Access Power Controller’s dual input design allows power to be steered from one (1) or two (2) independent low voltage 12 or 24 VDC Altronix power supplies to eight (8) independently controlled fuse (LINQ8ACM) or PTC (LINQ8ACMCB) protected outputs. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.
  • Page 3: Installation Instructions

    • FACP output relay [NC]: Either Dry 1A/28VDC, 0.6 Power Factor or 10K resistance with [EOL JMP] intact. Fuse Ratings: • Main input fuses rated 15A/32V each. • LINQ8ACM: Output fuses are rated 3A/32V. • LINQ8ACMCB: Output PTCs are rated 2A. LED Indicators: •...
  • Page 4 6. Output Options (program output options via LINQ software): LINQ8ACM(CB) will provide up to eight (8) switched power outputs plus eight (8) unswitched auxiliary power outputs. Switched Power outputs: Connect the negative (–) input of the device being powered to the terminal marked [COM].
  • Page 5 8-Pin Connector For connection to VR6 or Tango1B. U V W X Y Z Laptop connection enables LINQ8ACM(CB) initial setup and programming. Ethernet: LAN or laptop connection enables LINQ8ACM(CB) programming and V W X Y Z RJ45 status monitoring. W X Y Z PWR1+, PWR2+ Positive [+] plugs for spade connectors.
  • Page 6: Led Diagnostics

    12V (from VR6 regulator) 12VDC 12VDC (from external power supply) 11.7-12VDC 24VDC (from external power supply) 23.7-24VDC Maximum Output of Altronix Power Supplies: UL Listed or Recognized Power Supply Output Voltage Setting Max. Output Current eFlow4NB 12VDC or 24VDC eFlow6NB...
  • Page 7 4. Align 8-pin male connector with female receptacle of LINQ8ACM(CB), then mount. 5. Connect 24VDC power supply to terminal marked [+ PWR1 –] of LINQ8ACM(CB). Thus Input 1 of LINQ8ACM(CB) is 24VDC from power supply and Input 2 is determined by VR6’s settings (5VDC or 12VDC).
  • Page 8 4. Align 8-pin male connector with female receptacle of LINQ8ACM(CB), then mount. 5. Connect 24VDC power supply to terminal marked [+ PWR1 –] of LINQ8ACM(CB). Thus Input 1 of LINQ8ACM(CB) is 24VDC from power supply and Input 2 is determined by Tango1B’s settings (12VDC or 12VDC).
  • Page 9: Typical Application Diagram

    Power Supply 2 EN<-->DIS FACP (Fire Alarm Control Panel) NC COM NC COM NC COM NO NC COM NC COM NC COM NC COM NO NC COM Mag. Lock LINQ8ACM LINQ8ACMCB Electric Strike Electromagnetic Door Holders LINQ8ACM(CB) - 9 -...
  • Page 10: Network Settings

    Network Settings. Network Settings: In the IP Address Method field select the method by which the IP Address for the LINQ8ACM(CB) will be obtained: “STATIC” or “DHCP”, then follow the appropriate steps (contact the network administrator to determine which method will be used).
  • Page 11: Factory Default Settings

    1. Set the static IP address for the laptop to be used for programming to the same network IP address as the LINQ8PD(CB), i.e. 192.168.168.200 (default address of the LINQ8ACM(CB) is 192.168.168.168). 2. Connect one end of the network cable to the network jack on the LINQ8ACM(CB) and the other to the network connection of the laptop.
  • Page 12: Temperature Settings

    2. Click on the Configure IP Settings tab at the top of the screen to access the IP setup. 3. In the Method field use the pulldown menu select the method that the IP Address for the LINQ8ACM(CB) will be obtained: “Static” or “DHCP”, then follow the appropriate steps below.
  • Page 13: Cloud Settings

    After selecting DHCP in the Method field click the button labeled Submit. Next, click on the button labeled Reboot to save the settings. After rebooting the LINQ8ACM(CB) will be set in the DHCP mode. The IP address will be assigned by the router when the LINQ8ACM(CB) is connected to the network.
  • Page 14: Certificate Upload

    NOTE: A self-signed SSL certificate will be generated with the information provided in the “SSL Certificate Settings” fields. The certificate will be valid for 500 days, and time stamped with the time settings present on the LINQ8ACM(CB) module. The date and time must be synced with the host computer before generating an SSL certificate.
  • Page 15: Hookup Diagrams

    EOL Jumper [EOL JMP] should be installed in the EOL position. Latching Single Reset. N.O. Switch Fig. 8 - Daisy chaining one or more LINQ8ACM(CB) units. EOL Jumper [EOL JMP] should be installed in the EOL position. Latching Individual Reset. N.O.
  • Page 16 Switch Switch Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. MEMBER IILINQ8ACM(CB) K04S - 16 -...