Plena Voice Alarm System | Installation and User Instructions | Equipment
13.2

External connections

13.2.1 Voice alarm controller
Connect the fireman's panel to the voice alarm
controller (see section 5.3.5).
13.2.2 Remote control extensions
The remote controller has 1 socket for remote control
extensions (LBB1997/00, LBB1999/00). Use shielded
Cat-5 Ethernet cables with RJ45 plugs to connect a
remote control extension to the remote control. When
the system requires more than 1 remote control
extension, use the system sockets on the remote control
extension to make loop-throughs. See section 9.3.2 for
connection details.
13.2.3 Status output contacts
The remote control panel has 3 status output contacts to
indicate the current system state. The procedure for
connecting the status outputs is the same as the
procedure for connecting status outputs to the voice
alarm controller (see section 5.3.11).
13.2.4 Power
The procedure for connecting a fireman's panel to a
power supply is the same as the procedure for
connecting a remote control to a power supply (see
section 9.3.4).
13.3

Technical data

EMC emission:
According to EN55103-1
EMC immunity:
According to EN55103-2
Current consumption:
150 mA (idle)
400 mA (indicator test)
Dimensions:
132.5 x 430 x 90 mm
Weight:
2.2 kg
Bosch Security Systems | 2006-06 | 9922 141 10377 en