Shopping Mall - Bosch Plena Installation And User Instructions Manual

Voice alarm system
Table of Contents

Advertisement

Plena Voice Alarm System | Installation and User Instructions | Introduction
3.3

Shopping mall

3.3.1
Introduction
Shopping malls are typical example of applications with
a large number of zones with varying output power
requirements per zone. The priorities are speech
intelligibility and compliance with IEC60849 standard
(and its national equivalents). In addition to mandatory
voice alarm functionality for evacuating the public and
shop personnel, an EVAC system for shopping centers
can have BGM for the public areas. It should be
possible to individually call each shop or store. During
emergency messages, each shop's BGM volume control
is automatically overridden. Additional public address
functionality for making general public announcements
is an optional requirement.
3.3.2
Summary of requirements
Typically up to 60 zones
Speech intelligibility is the main priority
Variable power requirement per zone
Call station in security control room
Additional public address functionality
(non-emergency)
BGM in public areas
BGM music with local override in shops
3.3.3
Solution for a 54-zone system
A Plena Voice Alarm System Controller handles
routing to 6 zones, the remaining 48 zones require eight
6-zone routers. The security control room is equipped
with a remote control panel and call station plus
keypads for individually addressing zones and BGM for
the public areas, while the controller unit and routers
are located in a fire-resistant cabinet or basement.
Fireman's panel (with overall priority) is built in close to
the main entrance or emergency exit (subject to relevant
local regulations). The Plena Voice Alarm System is a
two-channel system, so BGM can still be provided in
zones not receiving a call.
Bosch Security Systems | 2006-06 | 9922 141 10377 en
3.3.4
Power requirements
Each zone will have varying power requirements,
ranging from small shops with a single loudspeaker to
department stores with several floors and more
loudspeakers. Parking garages and open-air walkways
will require weatherproof sound projectors or horn
loudspeakers. To facilitate phased evacuation from
different levels of the shopping center, public areas are
divided into zones. Additional Plena Power Amplifiers
are incorporated to provide additional power,
two-channel operation and for use as a spare amplifier.
3.3.5
Layout
See figure 3.3, table 3.5 and table 3.6
table 3.5: Zones
Zone
Description
Z1-30
30 small shops/kiosks
Z31-36
6 shops
Z37-42
6 medium-sized stores
Z47
Security control room
Z48
Offices
Z49
Walkways ground floor
Z50
Gallery 1st floor
Z51
Gallery 2nd floor
Z52
Main public square
Z53
Parking garage level 1
Z54
Parking garage level 2
Total
table 3.6: Units
Unit
Description
LBB1990/00
Controller
LBB1992/00
Router
LBB1996/00
Remote control
LBB1997/00
Remote control extension
LBB1956/00
Call station
LBB1957/00
Call station keypad
LBB1935/00
Power Amplifier (240 W)
LBB1938/00
Power Amplifier (480 W)
PLN-DVDT
DVD Tuner
en | 19
Power
30 x 6 W
12 x 6 W
24 x 6
1 x 6 W
4 x 6 W
4 x 6 W
10 x 6 W
10 x 6 W
4 x 18 W
6 x 10 W
6 x 10 W
858 W
No.
1 x
8 x
1 x
8 x
1 x
5 x
1x
2 x
1x

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents