Lbb1997/00 Remote Control Extension; Controls, Connectors And Indicators - Bosch Plena Installation And User Instructions Manual

Voice alarm system
Table of Contents

Advertisement

Plena Voice Alarm System | Installation and User Instructions | Equipment
11
LBB1997/00 Remote
Control Extension
11. 1
Controls, connectors and
indicators
See figure 11.1 for an overview of the controls,
indicators and connectors on the remote control
extension:
1 Power LED/VU Meter - A combined power
indicator and VU meter. The green power LED is lit
if the remote control extension is connected to the
mains or back-up power and switched on. The VU
meter indicates the call level: 0 dB (red), -6 dB,
-20 dB (yellow).
1
Plena Remote Control Extension
Fault Indicators
0 dB
Processor reset
Network
-6dB
Call/EMG
-20dB
Music/Spare
Ground short
Input
Power
24V
DC In
13
figure 11. 1 : Front and rear views of the remote control extension kit
Bosch Security Systems | 2006-06 | 9922 141 10377 en
2
A
B
Zone1
Mains
Zone2
Zone3
Battery
Zone4
Zone5
Zone6
Trigger Output
Fault
1
2
3
Termination
RCP ext. In
ID
Off
On
6
1...9
12
11
10
9
2 Fault indicators - Eight yellow system fault LEDs
(Processor reset, Network, Call/EMG, Music/Spare,
Ground short, Input, Mains, Battery) and twelve
yellow loudspeaker line fault LEDs. Fault indication
is only possible if supervision is enabled (see section
28.4).
3 Emergency call zone selectors - Six buttons to
select the zones to which the emergency call must be
distributed (see 27). Each button has a green and a
red LED. The six red LEDs indicate the zones that
are selected for the emergency call. The six green
LEDs indicate the zones in which a business call is
running.
4 BGM zone selectors - Six buttons to select the
zones to which the BGM is distributed (see 25). Each
button has a green LED. The six green LEDs
indicate the zones to which BGM is distributed.
Zone select
Zone1
Zone2
Zone select
RCP ext. Out
For service only
Off
On
Firmware
Upgrade
8
7
6
3
Zone3
Zone4
Zone5
4
PLN-V6RCE
8900 199 80001
Plena Voice Alarm System
RC Panel Extension
Max. input power
A035413
200mA, 24V DC
N663
S/N.
NL-4827HG-10
Design & Quality
The Netherlands
Warning
This apparatus must be earthed
5
en | 60
Alarm
Zone6