Bosch Plena Installation And User Instructions Manual page 42

Voice alarm system
Table of Contents

Advertisement

Plena Voice Alarm System | Installation and User Instructions | Equipment
5.4.4
Interconnection
Call Station (LBB1956/00):
RJ45 sockets, CAN bus
max. 8 call stations
Voice Alarm Router (LBB1992/00):
RJ45 socket, CAN bus
max. 9 routers
Remote controls (LBB1995, LBB1996, LBB1997):
RJ45 socket, CAN bus
max. 2 remote controls
PC:
USB 2.0 (USB 1. 1 compatible)
External power amplifier
3-pin XLR and screw terminals, max. 5 A
max. rated output 1000 W
5.4.5
Loudspeaker outputs
Type:
Screw terminals
Number of zones:
6
Number of loudspeaker lines:
12 (2 per zone)
Signal-to-noise ratio (flat at max. volume):
> 85 dB
Line voltage:
100 V
5.4.6
Overrides
Type:
3-wire or 4-wire on screw terminals
Voltage:
24 V(DC) for 4-wire, if selected
Current:
total 0.8 A
5.4.7
Trigger outputs
Type:
Screw terminals
Voltage:
Floating, max. 250 V
Current:
max. 0.5 A
Bosch Security Systems | 2006-06 | 9922 141 10377 en
5.4.8
Trigger inputs/24 V DC out
Trigger voltage:
< 24 V
Type:
Momentary or latching
Normally opened (default) or normally closed
Emergency input supervision:
10 kΩ + 10 kΩ series and parallel resistors
24 V DC out:
24 V(DC), max. 0.8 A
VOX switch:
Normally opened
5.4.9
Mic/line input with VOX
functionality
Type:
3-pin XLR, 6.3 mm jack socket, balanced
Sensitivity:
1 mV +1/-3 dB (mic), 1 V +1/-3 dB (line)
Impedance:
> 10 kΩ
VOX threshold:
500 µV (mic), 500 mV (line)
5.4.10 BGM
Type:
Cinch, stereo converted to mono
Nominal input level:
500 mV
5.4.11 Line out
Type:
3-pin XLR, 6.3 mm jack socket, balanced
Nominal output level:
1 V
Maximum output level:
1 V
5.4.12 External power amplifier
Type:
3-pin XLR and screw terminals
Controller output/Amplifier input:
1 V
Controller input/Amplifier output:
100 V
en | 42

Hide quick links:

Advertisement

Table of Contents
loading