Plena Voice Alarm System | Installation and User Instructions | Introduction
3

Application examples

3. 1

Schools

3.1.1
Introduction
Schools are typical example of applications with a large
number of zones each with a relatively low output
power requirement per zone. The main priorities are
speech intelligibility and compliance with IEC60849
standard (or equivalent). In addition to mandatory voice
alarm functionality for evacuating staff and students,
EVAC systems for schools should also include chime
tones for notifying the start/finish of lessons, plus public
address functionality for individually calling classrooms
or public area. BGM is not essential. Since a classroom
has a low ambient noise level, 1 loudspeaker is usually
sufficient, keeping the total power requirement
relatively low. Outside areas such as playgrounds and
sports fields will require weatherproof horn
loudspeakers.
3.1.2
Summary of requirements
Typically 20 to 60 zones (in high schools)
Speech intelligibility is the main priority
Low power requirement (1 loudspeaker) per
classroom
Fireman's panel by main entrance
Call station in main office
Additional public address functions such as chime
tones desirable
BGM in recreation areas is optional
3.1.3
Solution for a 30-zone system
The Plena Voice Alarm System Controller handles
message routing to 6 zones, the remaining 24 zones
require four additional 6-zone routers. The office is
equipped with a call station plus keypads for
individually addressing zones, while a fireman's panel
(with overall priority) is built in by the main entrance.
Bosch Security Systems | 2006-06 | 9922 141 10377 en
3.1.4
Power requirements
The system controller features a built-in 240 W power
amplifier, making it possible to drive up to 40
loudspeakers with a power handling capacity of 6 W
each. This is sufficient for a medium-sized high school
with 24 classrooms, 4 toilets/changing rooms, a staff
meeting room and 2 offices, each requiring a single
loudspeaker. The canteen, assembly hall, playing fields
and corridors typically require more loudspeakers per
zone. An additional Plena Power Amplifier is used as a
spare amplifier.
3.1.5
Layout
See figure 3.1, table 3.1 and table 3.2.
table 3. 1 : Zones
Zone
Description
Z1-22
Classrooms
Z23
Toilets/changing rooms
Z24
Staff meeting room
Z25-26
Offices
Z27
Corridors
Z28
Assembly hall
Z29
Lunch canteen
Z30
Playing fields
Total
table 3.2: Units
Unit
Description
LBB1990/00
Controller
LBB1992/00
Router
LBB1996/00
Remote control
LBB1997/00
Remote control extension
LBB1956/00
Call station
LBB1957/00
Call station keypad
LBB1935/00
Power Amplifier (240 W)
en | 15
Power
22 x 6 W
4 x 6 W
1 x 6 W
2 x 6 W
4 x 6 W
2 x 6 W
2 x 6 W
1 x 10 W
232 W
No.
1 x
4 x
1x
4x
1x
4x
1x