2.6.4
External power amplifiers
The voice alarm router does not have an internal power
amplifier. When the power that is supplied by the voice
alarm controller is insufficient, to each voice alarm
router two external power amplifiers can be connected.
In a multi-router system, multiple power amplifiers can
be connected to amplify calls and background music
(BGM) or just for backup purposes.
2.6.5
Remote control
With the LBB1997/00 Voice Alarm Remote Control
Extension, it is possible to control the voice alarm router
from another location. The remote control extension is
also available as a kit (LBB1999/00 Voice Alarm
Remote Extension Kit) for creating customized
solutions.
2.7

Call station

2.7.1
Introduction
The LBB1956/00 Call Station can be connected to the
Plena Voice Alarm System to make business calls. The
maximum number of call stations in a Plena Voice
Alarm System is 8.
figure 2.3: Call Station
Bosch Security Systems | 2006-06 | 9922 141 10377 en
2.7.2
Buttons
Each call station has zone select buttons and a
push-to-talk (PTT) button. The zone select buttons can
be configured for selecting zones and zone groups in the
system. To the PTT button, a pre- and post chime can
be assigned that is played at the start or at the end of the
business call.
2.7.3
Supervision
The call station is not supervised. For compliance to
evacuation standards, the Plena Voice Alarm System
disables the call station during emergency calls.
2.7.4
Keypad
Each voice alarm router can add 6 extra loudspeaker
zones to the system. To be able to distribute calls to the
extra zones, it is possible to connect LBB1957/00 to the
call station. The maximum number of keypads that can
be connected to a call station is 8.
figure 2.4: Call station keypad