Plena Voice Alarm System | Installation and User Instructions | Configuration
21
Call station
21. 1
Introduction
The call stations are configured using the DIP switch at
the bottom (see figure 21.1).
figure 21. 1 : Call station DIP switches
table 21. 1 : Call station DIP switches
DIP switch
Description
1, 2, 3, 4
Set the ID of the call station. See
section 21.2
5, 6
Set the sensitivity of the call station.
See section 21.3.
7
Switches the speech filter on (ON)
and off (OFF). See section 21.4.
8
Switches termination on (ON) and
off (OFF). See section 21.5.
21.2
Call station ID
The ID of the call station is set using switches 1 to 4.
Each call station must have a unique ID (1 to 9).
Bosch Security Systems | 2006-06 | 9922 141 10377 en
21.3
Sensitivity
The sensitivity of the call station is set using switches 5
and 6 (see table 21.2).
table 21.2: Call station sensitivity
Sensitivity
Switch 5
-15 dB
OFF
0 dB
OFF
6 dB
ON
Reserved
ON
21.4
Speech filter
If switch 7 is in the ON position, a speech filter is
activated for the call station. The speech filter improves
the speech intelligibility by cutting off the lower
frequencies.
21.5
Termination
The last call station in a sequence of looped-through call
stations must always be terminated. Only for these call
stations, put switch 8 in the ON position.
en | 82
Switch 6
OFF
ON
OFF
ON