6 Troubleshooting
Event name
NX Message Communications Error
Meaning
An error has occurred in message communications.
Source
PLC Function Module
EtherCAT Master Function Module
EtherNet/IP Function Module
NX Bus Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The communications cable is broken.
The communications cable connec-
tor is disconnected.
The NX message communications
load is high.
Attached
Attached information 1: System information
information
Attached Information 2: Type of communications
0: NX bus
1: EtherCAT
65,535: Unit internal communications (routing)
Precautions/
None
Remarks
Event name
PLC System Information
Meaning
This event provides internal information from the PLC Function Module.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
This event provides internal informa-
tion from the PLC Function Module. It
is recorded to provide additional infor-
mation for another event.
Attached
Attached information 1: System information
information
Attached Information 2: System information
Attached information 3: System information
Attached information 4: System information
Precautions/
None
Remarks
6 - 88
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Check the communications cable and
replace it if it is broken.
Reconnect the connector and make
sure it is mated correctly.
Reduce the number of times that
instructions are used to send NX
messages. Or, increase the value of
the TimeOut input variable to the
instruction. If more than one copy of
the Sysmac Studio is connected,
reduce the frequency of simultaneous
operations.
Source details
Information
Recovery
Continues.
Operation
Data type
---
Correction
---
Event code
80230000 hex
None
Detection
timing
---
Log category
---
Name
---
Prevention
Check the communications cable to
see if it is operating properly.
Make sure the communications cable
is connected properly.
Reduce the number of times that
instructions are used to send NX
messages. Or, increase the value of
the TimeOut input variable to the
instruction. If more than one copy of
the Sysmac Studio is connected,
reduce the frequency of simultaneous
operations.
Event code
40150000 hex
None
Detection
timing
---
Log category
Operation is not affected.
Name
---
Prevention
---
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)