5 Installation and Wiring
When you use any ferrules other than those in the above table, crimp them to the twisted wires so
that the following processed dimensions are achieved.
1.6 mm max.
(Terminals other than ground terminals)
2.0 mm max.
(Ground terminals)
 Using Twisted or Solid Wires
If you use twisted wires or solid wires, use the following table to determine the correct wire specifica-
tions.
Terminals
Classifica-
tion
All terminals
except
ground
terminals
Ground
terminals
*1. Secure wires to the screwless clamping terminal block. Refer to Securing Wires on page 5-51 for how to
secure wires.
Precautions for Correct Use
• Use cables with suitable wire sizes for the carrying current. There are also restrictions on the
current due to the ambient temperature. Refer to the manuals for the cables and use the
cables correctly for the operating environment.
• For twisted wires, strip the sheath and twist the conductor portion. Do not unravel or bend the
conductor portion of twisted wires or solid wires.
NG
Unravel wires
Additional Information
If more than 2 A will flow on the wires, use plated wires or use ferrules.
5 - 48
Twisted wires
Current
capacity
Plated
Unplated
2 A max.
Possible
Possible
Not pos-
Greater
than 2 A
sible
and 4 A or
less
---
Possible
Possible
8 to 10 mm
2.4 mm max.
(Terminals other than ground terminals)
2.7 mm max.
(Ground terminals)
Wire type
Solid wire
Plated
Unplated
Possible
Possible
Possible
Not possi-
*1
ble
Possible
Possible
NG
Bend wires
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
Conductor
Wire size
length (strip-
ping length)
0.08 to 1.5
8 to 10 mm
2
mm
(AWG
28 to 16)
2
10 to 12 mm
2.0 mm