 Analog Output
Terminal Block Wiring
 Wire and Ferrule
Attach a ferrule to a wire, or use a solid wire.
Do not connect bare stranded wires directly to terminals.
The recommended solid wire specification and ferrule are given below.
Recommended solid wire
Wire type
Solid Wire
Recommended ferrule
Manufacturer
Phoenix Contact
 Terminal Wiring
Release button
• To make the connection, press the release button in with a small flat blade screwdriver and push
the line in while the lock is released. Remove the screwdriver and lock it inside.
• To disconnect the wiring, press the release button in with a small flat blade screwdriver and pull
the line out while the lock is released.
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
V O 1
Analog output 1
V O 2
Analog output 2
COM()
Analog ground
Wire size
0.2 mm
to 0.5 mm
2
2
Model
AI-0.25-12
0.2 mm
2-conductor shielded
twisted-pair cable
(AWG24 to AWG20)
Applicable wire
2
(AWG24)
5 Installation and Wiring
5
5 - 71