Omron NX1P2 series User Manual page 275

Machine automation controller nx-series nx1p2 cpu unit
Hide thumbs Also See for NX1P2 series:
Table of Contents

Advertisement

Event name
NX Unit Initialization Error
Meaning
Initializing an NX Unit failed.
Source
NX Bus Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Initialization with the Unit configura-
tion information registered in the CPU
Unit failed.
An NX Bus Communications Error
has occurred.
The Channel Enable/Disable Setting
for all channels of the Analog Unit are
set to Disable.
Initialization of an NX Unit failed.
Attached
Attached information 1: Unit number of the NX Unit where the error occurred
information
Attached information 2: System information
Precautions/
None
Remarks
Event name
NX Unit Startup Error
Meaning
Starting an NX Unit failed.
Source
NX Bus Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
A startup error occurred in an NX
Unit.
Attached
Attached information 1: Mounting position of the NX Unit where the error occurred
information
Attached information 2: System information
Precautions/
None
Remarks
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Connect the Sysmac Studio and
reconfigure the Unit configuration
information in the CPU Unit.
Correct the NX Bus Communications
Error.
Set the Channel Enable/Disable Set-
ting to Enable for at least one chan-
nel.
Cycle the power supply to the rele-
vant NX Unit. If this error persists,
replace the NX Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Cycle the power supply to the rele-
vant NX Unit. If this error persists,
replace the NX Unit.
6 Troubleshooting
Event code
85520000 hex
Master
Detection
timing
Error reset
Log category
For NX Units with this error, I/O communications will not
operate, but message communications can be performed.
Name
---
Prevention
Download the Unit configuration infor-
mation to the CPU Unit and the NX
Unit.
Take preventive measures against
the NX Bus Communications Error.
For an Analog Unit, set the Channel
Enable/Disable Setting to Enable for
at least one channel.
For an Analog Unit, set the Channel
Enable/Disable Setting to Enable for
at least one channel.
Event code
85530000 hex
Master
Detection
timing
Cycle the power
Log category
supply to the
CPU Unit or reset
the Controller.
For NX Units with this error, I/O communications will not
operate and message communications cannot be per-
formed.
Name
---
Prevention
None
At CPU Unit
power ON, at
Controller reset,
at NX bus restart,
or at error reset
System
6
At CPU Unit
power ON, at
Controller reset,
at NX bus restart,
or at error reset
System
6 - 57