Event code
Event name
10270000 hex
Error in Start-
ing Automatic
Transfer
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
Meaning
Assumed cause
An error was
• An SD Memory Card is not
detected in pre-
inserted.
execution checks
• The SD Memory Card type is
for automatic trans-
not correct.
fer.
• The format of the SD Memory
Card is not correct.
• There is no autoload folder on
the SD Memory Card.
• There are no backup files in the
autoload folder on the SD
Memory Card.
• Either the backup files in the
autoload folder on the SD
Memory Card are corrupted or
required data is not in the
backup files on the SD Memory
Card.
• The unit version of the CPU
Unit to which to transfer the
files is older than the unit ver-
sion of the backup files on the
SD Memory Card.
• The model of the CPU Unit to
which to transfer the files is not
the same as the model of the
CPU Unit of the backup files on
the SD Memory Card.
• Recovery was executed for the
SD Memory Card.
• The CPU Unit is write-pro-
tected.
• The settings in the automatic
transfer command file (Auto-
loadCommand.ini) are not cor-
rect.
• Reading the data for automatic
transfer failed because the SD
Memory Card is faulty or not
formatted correctly.
• The SD Memory Card is dam-
aged.
• The database connection ser-
vice version of the CPU Unit to
which to transfer the files is
older than the database con-
nection service version of the
backup files on the SD Memory
Card.
• The robot version of the CPU
Unit to which to transfer the
files is older than the robot ver-
sion of the backup files on the
SD Memory Card.
6 Troubleshooting