B.8 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
H5-09
Communication Fault
(0435)
Detection Time
Unit Selection for
H5-10
MEMOBUS/Modbus
(0436)
Register 0025H
Communications
H5-11
ENTER Function
(043C)
Selection
H5-12
Run Command Method
(043D)
Selection
H5-13
Power-up CALL Alarm
(043E)
H5-14
(0FB4) Communication Error
(CE) Go-To- Frequency
H5-15
(0FB5) Communication Error
(CE) Go-To-Timeout
H5-16
Communication Error
(0FB6)
Fault Restart Selection
Operation Selection
H5-17
when Unable to Write
(11A1)
into EEPROM
H5-18
Filter Time Constant for
(11A2)
Motor Speed Monitoring
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
u

H6: Pulse Train Input

No.
(Addr.
Name
Hex)
Pulse Train Input
H6-01
Terminal RP Function
(042C)
Selection
H6-02
(042D) Pulse Train Input
Scaling
H6-03
(042E) Pulse Train Input Gain
312
LCD Display
Sets the time required to detect a communications error.
CE Detect Time
Adjustment may be needed when networking several drives.
CommReg 25h Unit
0: 0.1 V units
0: 0.1 V
1: 1 V units
1: 1 V
0: Drive requires an Enter command before accepting any
Enter CommandSel
changes to parameter settings.
0: Enter Required
1: Parameter changes are activated immediately without the
1: No EnterRequired
Enter command (same as V7).
Run CommandSel
0: FWD/Stop, REV/Stop
0: FWD Run &REV
1: Run/Stop, FWD/REV
Run
1: Run & FWD/REV
Determines whether a CALL alarm is triggered at power-up
Powr-up CALL Alm
when communication with the external controller has not been
0: Disabled
established.
1: Enabled
0: Disabled
1: Enabled
Sets the speed at which the drive will run when H5-04 is set to
CE Go-To-Freq
4 (Run at H5-14) and a CE error is present.
Sets the amount of time that the drive will run at the speed set
in H5-14 before triggering a CE fault when H5-04 is set to 4
CE Go-To-Timeout
(Run at H5-14) and a CE error is present.
Setting this parameter to 0 will disable the time-out.
CE Fault Restart
Determines whether the CE fault can be restarted (L5-01).
0: No Retry
0: No Retry
1: Retry
1: Retry
Selects operation when an attempt is made to write data into
EEPROM via MEMOBUS/Modbus communications and
Busy Enter Sel
writing into EEPROM is not possible.
0: No ROM Enter
There is normally no need to change this parameter from the
1: RAM Enter
default value
0: Cannot write into EEPROM
1: Write in RAM only
Sets the filter time constant for monitoring the motor speed
from MEMOBUS/Modbus communications and
MtrSpd Monitor T
communication options.
Applicable MEMOBUS/Modbus registers are: 3EH, 3FH,
44H, ACH, and ADH
LCD Display
0: Frequency reference
Term RP Func Sel
1: PID feedback value
0: Frequency Ref
2: PID setpoint value
1: PID Feedback
5: Flow meter
2: PID Set Point
Note:
5: Flow Meter
Sets the terminal RP input signal frequency that is equal to
100% of the value selected in H6-01.
Term RP Scaling
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
Terminal RP Gain
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
Description
Description
When this parameter is set to 5, parameters
H6-02 to H6-04 and H6-08 are ignored.
Values
Page
Default: 2.0 s
Min.: 0.0
Max.: 10.0
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
Default: 0 s
Min.: 0
Max.: 6000
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0 ms
Min.: 0
Max.: 100
Values
Page
Default: 0
Range: 0 to 2; 5
Default: 1440 Hz
Min.: 100
Max.: 32000
Default: 100.0%
Min.: 0.0
Max.: 1000.0