L3: Stall Prevention - YASKAWA U1000 iQpump MATRIX Drive User Manual

Low harmonic regenerative pump controller
Hide thumbs Also See for U1000 iQpump MATRIX Drive:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Momentary Power Loss
L2-07
Voltage Recovery
(048B)
Acceleration Time
L2-13
Input Power Frequency
(04CD)
Fault Detection Gain
L2-21
Low Input Voltage
(04D5)
Detection Level
Power Supply
L2-27
Frequency Fault
(04F7)
Detection Width
<1> Default setting is determined by parameter o2-04, Drive Model Selection.
<2> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
u

L3: Stall Prevention

No.
(Addr.
Name
Hex)
Stall Prevention
L3-01
Selection during
(048F)
Acceleration
L3-02
Stall Prevention Level
(0490)
during Acceleration
Stall Prevention Limit
L3-03
during Acceleration/
(0491)
Deceleration
Stall Prevention
L3-04
Selection during
(0492)
Deceleration
L3-05
Stall Prevention
(0493)
Selection during Run
L3-06
Stall Prevention Level
(0494)
during Run
L3-14
Stall Prevention Level
(04E9)
during Deceleration
Automatic Reduction
L3-23
Selection for Stall
(04FD)
Prevention during Run
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
LCD Display
Sets the time to accelerate to the frequency reference when
momentary power loss is over. If set to 0.0, the active acceleration
KEB Accel Time
time (C1-01, C1-03, C1-05) is used.
FDV Detect Gain
Set the gain to use to detect power supply frequency fault (Fdv).
AVV Detect Level
Set the level at which to detect a low input voltage.
Sets the frequency width to use to detect power supply frequency
FDV Detect Width
fault (Fdv).
LCD Display
0: Disabled.
StallP Accel Sel
1: Enabled. General purpose. Acceleration is paused as long as
0: Disabled
the current is above the L3-02 setting.
1: General Purpose
3: Enabled (Current Limit). The acceleration rate is automatically
3: iLim Mode
adjusted while limiting the output current at the setting value of
the stall prevention level (L3-02).
Used when L3-01 = 1 or 3. 100% is equal to the drive rated
current.
StallP Accel Lvl
Sets Stall Prevention lower limit during acceleration/deceleration
StallPAcc LowLim
when operating in the constant power range. Set as a percentage
of drive rated current.
0: Disabled. Deceleration at the active deceleration rate. An ov
fault may occur.
StallP Decel Sel
1: General purpose. Deceleration is paused when the output
0: Disabled
current exceeds the Stall Prevention level.
1: General Purpose
4: Overexcitation Deceleration. Decelerates while increasing the
4: High Flux Brake
motor flux.
6: iLim Mode
6: Enable (Current Limit). The deceleration rate is automatically
adjusted while limiting the regeneration current at the setting
value of the stall prevention level (L3-14).
0: Disabled. Drive runs at a set frequency. A heavy load may
StallP Run Sel
cause stalling.
0: Disabled
1: Decel time 1. Uses the deceleration time set to C1-02 while
1: Decel Time 1
Stall Prevention is performed.
2: Decel Time 2
2: Decel time 2. Uses the deceleration time set to C1-04 while
Stall Prevention is performed.
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive
rated current.
StallP Run Level
Used when L3-04 = 1 or 6. 100% is equal to the drive rated
StallP Decel Lvl
current.
0: Sets the Stall Prevention level set in L3-04 that is used
CHP Stall P Sel
throughout the entire frequency range.
0: Lv1 set in L3-06
1: Automatic Stall Prevention level reduction in the constant
1: Autom. Reduction
output range. The lower limit value is 40% of L3-06.
B.9 L: Protection Function
Description
Description
Values
Page
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
<2>
Default: 1.0
Min.: 0.1
Max.: 2.0
Default: 150 V
<3>
Min.: 100 V
Max.: 230 V
<3>
Default: 6.0 Hz
Min.: 3.0 Hz
Max.: 20.0 Hz
Values
Page
Default: 1
Range: 0, 1, 3
<1>
Default:
Min.: 0%
<1>
Max.: 150%
Default: 50%
Min.: 0
Max.: 100
Default: 0
Range: 0 to 6
Default: 0
Range: 0 to 2
<1>
Default:
Min.: 30%
<1>
Max.: 150%
<1>
Default:
Min.: 80%
<1>
Max.: 200%
Default: 0
B
Range: 0, 1