Rtd Protection Module - Eaton EMR-5000 Installation, Operation And Maintenance Manual

Motor relay
Table of Contents

Advertisement

RTD Protection Module

Elements:
RTD
General – Principle Use
The protective device provides tripping and alarming functions based on the direct temperature measurements read
from Eaton's (URTD) device that has 11 temperature sensor channels or Eaton's (URTDII) device that has 11 or 12
temperature sensor channels. Each channel will have one trip function without an intended delay and one alarm
function with a delay.
•The "trip" function has only a threshold setting.
•Each individual »A larm Function« will have a threshold setting range, and can be individually enabled or disabled.
Since the temperature cannot change instantaneously (which is a way that temperature differs from current), the "delay"
is essentially built in to the function due to the fact that the temperature will take some time to increase from room
temperature to the "trip threshold" level.
•The dropout ratio for both trip and alarm is 0.99.
•The temperature rise is limited by the RTD driver.
•The entire function can be turned off or on, or individual channels can be turned off or on.
Voting
Additionally, RTD voting schemes are available and User programmable. The Voting feature must be activated and
configured within the following menu, [Protection Para\Set[x]\Temp-Prot/ RTD\Vote[x]]. Here, the setting » Function«
has to be set to » Active« .
Once activated, the number of channels that will be used by the voting feature is selected. This is set by way of the
parameter » Voting[x]« . This parameter defines how many of the selected channels must be over its threshold level in
order to get a voting trip. Each individual channel must be selected or deselected by setting to either » Yes« or » No« .
When selecting » Yes« , the channel will be used in the voting process. Note that in order to be selected, each channel
must also be active and the RTD module itself has to be active.
If for example, Vote[x] is set to » 3« , and all channels are set to » Yes« , and if any three of the selected channels exceed
The Resistance-based Temperature Detector (RTD) Protection Module uses
temperature data that are provided by Eaton's Universal Resistance-based
Temperature Detector (URTD) module (please refer to the URTD Module
section) or Eaton's Universal Resistance-based Temperature Detector II
(URTDII) module (please refer to the URTDII Module section).
If voting trip is required, please map the output used for tripping purposes:
"RTD. Voting Trip Grp 1" or "RTD.Voting Trip Grp 2"
EMR-5000
www.eaton.com
IM02602012E
757

Advertisement

Table of Contents
loading

Table of Contents