Emc Immunity Tests - Eaton EMR-5000 Installation, Operation And Maintenance Manual

Motor relay
Table of Contents

Advertisement

EMC Immunity Tests

Fast Transient Disturbance Immunity Test (Burst)
IEC 60255-22-4
IEC 61000-4-4
ANSI C37.90.1
class 4
Surge Immunity Test (Surge)
IEC 60255-22-5
IEC 61000-4-5
class 4
class 3
EMR-5000
Power supply, mains inputs
Other in- and outputs
Within one circuit
Circuit to ground
Communication cables to ground
www.eaton.com
±4 kV, 2.5 kHz
±2 kV, 5 kHz (coupling network)
±4 kV, 2.5 kHz (coupling clamp)
2 kV
4 kV
2 kV
IM02602012E