System Parameters – Voltage Related
Parameter
Description
Main VT pri
Enter the primary phase to phase voltage of the VTs
Main VT sec
Enter the secondary phase to phase voltage of the VTs
Main VT con
Main VTs connection
Aux VT pri
Primary voltage of Aux VTs
Aux VT sec
Secondary voltage of Aux VTs
delta phi - Mode
The delta phi element (vector surge) trips, if the
permissable voltage angle shift (delta phi) of the three
measured voltages (phase-ground or phase-phase) in:
one phase, two phases or within all phases is exceeded.
EMR-5000
Setting range
60 - 500000V
60.00 - 600.00V
Wye,
Phase-to-Phase,
Open-Delta
60 - 500000V
35.00 - 600.00V
one phase,
two phases,
three phases
www.eaton.com
IM02602012E
Default
Menu path
12000V
[System Para
/General Settings]
120V
[System Para
/General Settings]
Wye
[System Para
/General Settings]
12000V
[System Para
/General Settings]
120V
[System Para
/General Settings]
two phases
[System Para
/General Settings]
399