Canada; Europe; B.7 Canada - Emerson Rosemount 702 Reference Manual

Wireless discrete transmitter
Hide thumbs Also See for Rosemount 702:
Table of Contents

Advertisement

Reference Manual
00809-0200-4702, Rev DA
Special Conditions for Safe Use (X):
1. The Model 702 Transmitter housing contains
aluminum and is considered a potential risk of ignition
by impact or friction. Care must be taken into account
during installation and use to prevent impact and
friction.
2. The surface resistivity of the polymeric antenna is
greater than 1 GΩ. To avoid electrostatic charge
build-up, it must not be rubbed or cleaned with
solvents or a dry cloth.
3. For use only with the Model 701P or Rosemount P/N
753-9220-XXXX Smart Power Battery Module.
Sensor terminal
parameters
(option code 32)
U
= 6.51 V
o
I
= 13.37 mA
o
P
= 21.76 mW
o
C
= 21.77 μF
o
L
= 198 mH
o
N5 FM Nonincendive
Certificate: 3031506
Standards: FM Class 3600 - 1998, FM Class 3611 -
2004, FM Class 3810 - 2005, ANSI/NEMA
250 - 2003
Marking:
NI CL I, DIV 2, GP A, B, C, D T4;
T4(-50 °C ≤ T
Rosemount drawing 00702-1000; Type
4X; IP66.
Special Condition for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N
753-9220-XXXX Smart Power Battery Module.

B.7 Canada

I6
CSA Intrinsically Safe
Certificate: 1143113
Standards: AN/CSA C22.2 No. 0-10, CAN/CSA C22.2
No. 94-M91, CSA Std C22.2 No.
142-M1987, CSA Std C22.2 No. 157-92,
CSA Std C22.2 No. 60529:05
Markings:
Intrinsically Safe Class I, Division 1, Groups
A, B, C and D, T3C; suitable for Class 1,
Zone 0, IIC, T3C; when connected per
Rosemount drawing 00702-1020; Type
4X.
Product Certifications
Fuel sensor terminal
parameters
(option code 61)
U
= 7.8 V
o
I
= 92 mA
o
P
= 180 mW
o
C
= 9.2 μF
o
L
= 50 mH
o
≤ +70 °C) when installed per
a
N6 CSA Class I Division 2
Certificate: 1143113
Standards: CAN/CSA C22.2 No. 0-10, CAN/CSA C22.2
No. 94-M91, CSA Std C22.2 No.
142-M1987, CSA Std C22.2 No. 60529:05
Markings:
Suitable for Class 1, Division 2, Groups A,
B, C, and D, T3C; Cl. I, Zone 2, IIC, T3C.
B.8 Europe
I1
ATEX Intrinsic Safety
Certificate: Baseefa07ATEX0239X;
Standards: IEC 60079-0: 2011, IEC 60079-11: 2012
Markings:
II 1 G Ex ia IIC T4 Ga,
T4(–60 °C ≤ T
For use with Rosemount SmartPower power module
part number 753-9220-0001, or for use with Emerson
SmartPower option 701PBKKF.
Sensor terminal
parameters
(option code 32)
U
= 6.51 V
o
I
= 13.4 mA
o
P
= 21.76 mW
o
C
= 0.216 μF
i
C
= 21.78 μF
oIIC
C
= 549.78 μF
oIIB
C
= 1000 μF
oIIA
L
= 0
i
L
= 200 mH
oIIC
L
= 800 mH
oIIB
L
= 1000 mH
oIIA
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 GΩ. To avoid electrostatic change build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
IU
ATEX Intrinsic Safety for Zone 2
Certificate: Baseefa12ATEX0122X;
Standards: IEC 60079-0: 2011, IEC 60079-11: 2012
3G Ex ic IIC T4 Gc (–60 °C ≤ T
Markings:
Ex ic IIC T5 Gc, T5(–60 °C ≤ T
Switch terminal parameters
Input
Output
U
= 26 V
U
i
I
= 100 mA
I
i
o
P
= 0.65 W
P
i
o
N/A
C
N/A
L
o
Product Certifications
≤ +70 °C)
a
Fuel sensor terminal
parameters
(option code 61)
U
= 7.8 V
o
I
= 92 mA
o
P
= 180 mW
o
C
= 10 nF
i
C
= 9.2 μF
oIIC
C
= 129 μF
oIIB
C
= 1000 μF
oIIA
L
= 0
i
L
= 4.2 mH
oIIC
L
= 16.8 mH
oIIB
L
= 33.6 mH
oIIA
a
≤ +40 °C)
a
= 6.6 V
o
= 13.4 mA
= 21.8 W
= 10.9 μF
o
= 25 μH
July 2017
≤ +70 °C)
106

Advertisement

Table of Contents
loading

Table of Contents