Safety Shower And Eye Wash Monitoring - Emerson Rosemount 702 Reference Manual

Wireless discrete transmitter
Hide thumbs Also See for Rosemount 702:
Table of Contents

Advertisement

Reference Manual
00809-0200-4702, Rev DA
Figure 7-12. Dual Output Circuits with One Power Supply
Switching greater currents or voltages
It is important to note that the maximum output switching capacity is 26 volts DC and 100 milliamps. If a
greater voltage or current is to be switched, an interposing relay circuit can be used.
an example of a circuit to switch higher currents or voltages.
Figure 7-13. Wiring an Interposing Relay to Switch Greater Currents or Voltages
7.3.4

Safety shower and eye wash monitoring

The Rosemount 702 Transmitter can be used to monitor safety showers and eye wash stations by using
switch kits provided by TopWorx
transmitter model code and are available for both insulated and un-insulated pipes. These kits contain
the switches, brackets and cables that are necessary to install the transmitter to monitor both the safety
shower and the eye wash in a single station. Because each has two input channels, one transmitter can
be used to monitor both a safety shower and an eye wash.
Each Safety Shower Monitoring kit contains:
Two TopWorx Go Switch magnetic proximity switches
Two cables, one six foot and one 12 foot
Two black polymer cable glands
Mounting kit for safety shower and eye wash
Mounting, Wiring Switches, and Output Circuits: Models 702DX32 and 702DX42
Mounting, Wiring Switches, and Output Circuits:
, an Emerson company. These kits are ordered as a part of the
Models 702DX32 and 702DX42
Figure 7-13
July 2017
shows
67