Summary of Contents for Emerson Rosemount 708

  • Page 1 Quick Start Guide 00825-0200-4708, Rev DA June 2016 ™ Rosemount 708 Wireless Acoustic Transmitter...
  • Page 2: Table Of Contents

    Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount 708. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations. Refer to the Rosemount 708 Reference Manual (document number 00809-0100-4708) for more instruction. This guide and the manual are available electronically on www.rosemount.com.
  • Page 3: Overview

    Smart Wireless Gateway should be installed and functioning properly before any wireless devices are powered. Install the power module, Smart Wireless 701PGNKF into the Rosemount 708 to power the device. This results in a simpler and faster network installation. Enabling active advertising on the Gateway ensures new devices are able to join the network faster.
  • Page 4: Physical Installation

    4.1 Mounting For high temperature mounting, see page 1. Locate the Rosemount 708 on a horizontal section of piping as close as possible to the equipment to be monitored. Align the waveguide of the transmitter as shown in Figure 4 Figure 2.
  • Page 5 Quick Start Guide June 2016 5. Ensure the power module cover is fully tightened to prevent moisture ingress. The lip of the polymer power module cover should be in contact with the surface of the polymer enclosure to ensure a proper seal. Do not over tighten. Figure 4.
  • Page 6 Quick Start Guide 3. Tighten each screw to 90 in-lb (10,2 N-m). 4. Locate the Rosemount 708 and high temperature mounting hardware on a horizontal section of the piping as close as possible to the equipment to be monitored. The mounting location should be free of foreign matter and corrosion to ensure good contact between the piping and the mounting hardware.
  • Page 7: Mounting Considerations

    Quick Start Guide June 2016 Figure 8. Rosemount 708 Acoustic Transmitter with High Temperature Standoff and Fastener Kit 6.86 (174) 1.81 (46) 3.80 (97) A. For pipe sizes 0.5 to 2.5-in. Dimensions are in inches (millimeters). 4.3 Mounting considerations 1. Mounting bands should be inspected periodically and re-tightened if necessary.
  • Page 8: Device Network Configuration

    June 2016 Quick Start Guide Figure 9. Piping Insulation Side View 1-in. 5.0 Device network configuration In order to communicate with the Smart Wireless Gateway, and ultimately the information system, the transmitter must be configured to communicate with the wireless network. This step is the wireless equivalent of connecting wires ®...
  • Page 9: Verify Operation

    Smart Wireless Gateway’s integrated web interface, or by using AMS Suite Wireless Configurator or AMS Device Manager. If the Rosemount 708 was configured with the network ID and join key, and sufficient time has passed, the transmitter will be connected to the network. If network ID and join key were not configured, reference “Troubleshooting”...
  • Page 10 When the device has joined the network, it will appear in the Device Manager as illustrated in Figure 12. For HART protocol Wireless transmitter communication, a 708 DD is required. To obtain the latest DD, visit the Emerson Process Management Easy Upgrade site at: http://www2.emersonprocess.com/en-US/documentation/deviceinstallkits. Figure 12. Device Manager...
  • Page 11: Troubleshooting

    Quick Start Guide June 2016 Note ™ SteamLogic software is provided for viewing steam trap status. Refer to the manual on the CD for more information. 6.4 Troubleshooting If the device is not joined to the network after power up, verify the correct configuration of the network ID and join key, and that active advertising has been enabled on the Smart Wireless Gateway.
  • Page 12 Quick Start Guide 6.5 Field Communicator use Note In order to communicate with a Field Communicator, power the Rosemount 708 by connecting the power module. For more information on the power module, refer to the Product Data Sheet (document number 00813-0100-4701).
  • Page 13: Product Certifications

    RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
  • Page 14 June 2016 Quick Start Guide Special Conditions for Safe Use (X): 1. The Rosemount 708 shall only be used with the 701PGNKF Rosemount ™ SmartPower Battery Pack. 2. Potential Electrostatic charging Hazard — See Instructions. Canada I6 CSA Intrinsically Safe Certificate: 2439890 Standards: CAN/CSA C22.2 No.
  • Page 15 Quick Start Guide June 2016 China I3 China Intrinsic Safety Certificate: GYJ13.1445X Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings: Ex ia IIC Ga T4, –40 ~ +70 °C Special Condition for Safe Use (X): 1. See certificate for special conditions. Japan I4 TIIS Intrinsic Safety Certificate: TC20395 Markings: Ex ia IIC T4 X (–20 ~ +60 °C) EAC - Belarus, Kazakhstan, Russia...
  • Page 16 June 2016 Quick Start Guide Figure 15. Rosemount 708 Declaration of Conformity...
  • Page 17 Quick Start Guide June 2016...
  • Page 18 June 2016 Quick Start Guide...
  • Page 19 Quick Start Guide June 2016 China RoHS Rosemount 708 List of Parts with China RoHS Concentration above MCVs Rosemount 708 / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 20 +65 6777 0947 Enquiries@AP.EmersonProcess.com Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspx The Emerson logo is a trademark and service mark of Emerson Middle East and Africa Regional Office Electric Co. Emerson Process Management AMS, SmartPower, SteamLogic, Rosemount, and Rosemount Emerson FZE P.O.