  • Page 1 Reference Manual 00809-0100-4708, Rev AD September 2012 Rosemount 708 Wireless Acoustic Transmitter www.rosemount.com Get other manuals https://www.bkmanuals.com...
  • Page 2 Get other manuals https://www.bkmanuals.com...
  • Page 3 The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact an Emerson Process Management Sales Representative. Get other manuals https://www.bkmanuals.com...
  • Page 4 NOTICE The Rosemount 708 and all other wireless devices should be installed only after the Smart Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the Smart Wireless Gateway, beginning with the closest.
  • Page 5: Table Of Contents

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Table of Contents SECTION 1 Safety Messages ........1-1 Warnings .
  • Page 6 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 APPENDIX A Specifications ......... . . A-1 Functional Specifications.
  • Page 7: Safety Messages

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Section 1 Overview Safety Messages ........page 1-1 Overview .
  • Page 8: 708 Transmitter

    Gain instant visibility to all of your critical steam traps and PRVs ® through a non-intrusive, WirelessHART monitoring system • Know you are backed by Emerson’s proven experience in Smart Wireless field instrumentation and expert technical support Figure 1-1. Rosemount 708 Wireless Acoustic Transmitter Overview Power Module cover –...
  • Page 9: Wireless Considerations

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Wireless Considerations Power Up Sequence The Smart Wireless Gateway (Gateway) should be installed and functioning properly before any wireless devices are powered. Install the power module, SmartPower Solutions, model number 701PGN green power module, into the 708 to power the device.
  • Page 10: Mechanical

    Electrical Power Module The Rosemount 708 Wireless Acoustic Transmitter is self-powered. The power module contains one “D” size primary lithium/thionyl chloride battery. Each battery contains approximately 5.0 grams of lithium. Under normal conditions, the battery materials are self-contained and are not reactive as long as the battery and the power module are maintained.
  • Page 11: Service Support

    To expedite the return process outside of North America, contact your Emerson Process Management representative. Within the United States, call the Emerson Process Management Response Center toll-free number 1 800 654 7768. The center, which is available 24 hours a day, will assist you with any needed information or materials.
  • Page 12: Product Recycling/Disposal

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 PRODUCT Recycling of equipment and packaging should be taken into consideration. The product and packaging should be disposed of in accordance with local RECYCLING/DISPOSAL and national legislation. Get other manuals https://www.bkmanuals.com...
  • Page 13: Safety Messages

    Remove the power module cover and connect to the HART communication terminals for configuration. CONFIGURATION The Rosemount 708 will receive HART communication from a handheld 375/475 Field Communicator (Field Communicator) or AMS Wireless Configurator. When using a Field Communicator, any configuration changes must be sent to the transmitter using the Send key (F2).
  • Page 14: Device Network Configuration

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 ® Wireless Configurator AMS Wireless Configurator is capable of connecting to devices directly, using a HART modem, or remotely using the Gateway. To configure the Rosemount 708, double click (or right click and select Configure/Setup) on the device icon that will appear below either the HART modem or Gateway connection tree.
  • Page 15: Fast Key Sequence

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Fast Key Sequence Table 2-1 lists the fast key sequence for common transmitter functions. Table 2-1. 708 Fast Key Function Key Sequence Menu Items Sequence Device Information 2, 2, 5 Tag, Long Tag, Descriptor, Message, Date,...
  • Page 16: Hart Menu Tree

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 HART MENU TREE Figure 2-2. Field Communicator Menu Tree Get other manuals https://www.bkmanuals.com...
  • Page 17: Safety Messages

    Reference Manual 00809-0100-4708, Rev AD September 2012 Rosemount 708 Section 3 Mounting Safety Messages ....... . . page 3-1 Mounting .
  • Page 18 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Figure 3-1. Transmitter Alignment Figure 3-2. Transmitter Alignment Top View Figure 3-3. Power Module Installation NOTE: Wireless devices should be powered up in order of proximity from the Gateway, beginning with the closest device to the Gateway. This will result in faster network formation.
  • Page 19: Mounting Considerations

    Reference Manual 00809-0100-4708, Rev AD September 2012 Rosemount 708 Mounting Mounting bands should be inspected periodically and retightened if necessary. Some loosening may occur after initial installation due to Considerations thermal expansion/contraction. The waveguide must be in direct contact with the pipe.
  • Page 20 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Get other manuals https://www.bkmanuals.com...
  • Page 21: Safety Messages

    Suite Wireless Configurator or AMS Device Manager. If the Rosemount 708 was configured with the Network ID and Join Key, and sufficient time has passed, the transmitter will be connected to the network. If Network ID and Join Key were not configured, please reference Troubleshooting on page 4-3.
  • Page 22: Field Communicator

    When the device has joined the network, it will appear in the Device Manager as illustrated in Figure 4-2. For HART Wireless transmitter communication, a 708 DD is required. To obtain the latest DD, visit the Emerson Process Management Easy Upgrade site at: http://www2.emersonprocess.com/en-US/documentation/deviceinstallkits.
  • Page 23 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 NOTE SteamLogic software is provided for viewing steam trap status. Refer to the manual on the CD for more information. Troubleshooting If the device is not joined to the network after power up, verify the correct configuration of the Network ID and Join Key, and that Active Advertising has been enabled on the Gateway.
  • Page 24: Field Communicator Use

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Field Communicator Use NOTE In order to communicate with a Field Communicator, power the 708 by connecting the Power Module. For more information on the Power Module, refer to the Power Module product data sheet (Document No 00813-0100-4701).
  • Page 25: Safety Messages

    The acoustic energy is reported in 'counts,' which are a relative indication of the magnitude of the acoustic energy sensed. The acoustic sensor used in the Rosemount 708 is sensitive to a broad range of spectral frequencies in order to work in many different installations. The acoustic measurement or “count”...
  • Page 26: Alerts

    Rosemount 708 September 2012 ALERTS The Rosemount 708 can be configured to report alerts based on the acoustic and temperature level measured. The Rosemount 708 also reports diagnostic alerts when there is a device malfunction. For information on these alerts, refer to Section 6: Troubleshooting.
  • Page 27 September 2012 Device Alert Alert Levels Configuration The Rosemount 708 provides 4 user configurable alerts. Acoustic High - Triggers when acoustic level exceeds a user configured threshold. Acoustic Low - Triggers when acoustic level falls below a user configured threshold.
  • Page 28 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Figure 5-4. Install and Learn Alert Setup screen Alert Setup - Guided User Alert Setup Guided user alert setup cycles through on-screen prompts to set the alert levels. At each screen, the current level will be shown along with a box to enter the desired alert level as seen in Figure 5-5.
  • Page 29 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Figure 5-6. Manual Alert Setup screen If a device is installed and shows an unexpected alert, verify the installation conditions. POWER MODULE Expected power module life is ten years at reference conditions.
  • Page 30 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Shipping Considerations The unit was shipped to you without the power module installed. Please remove the power module prior to shipping. Each power module contains one “D” size primary lithium battery. Primary lithium batteries are regulated in transportation by the U.S.
  • Page 31 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Section 6 Troubleshooting Overview ........page 6-1 Safety Messages .
  • Page 32 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Table 6-1. Maintenance and Troubleshooting Suggestions Symptom Corrective Actions Device Troubleshooting Electronics Failure 1. Reset the device. 2. Reconfirm all configuration items in the device. 3. If the condition persists, replace the device.
  • Page 33: Specifications

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Appendix A Specifications and Reference Data Specifications ........page A-1 Dimensional Drawings .
  • Page 34: Performance Specifications

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Weight 708 with power module -0.595 kg (1.31 lb) 708 without power module - 0.445 kg (0.98 lb) Enclosure ratings NEMA 4X and IP66/67 Performance Vibration Effect Specifications Tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10-60 Hz 0.21 mm displacement peak amplitude/60-2000 Hz 3g).
  • Page 35: Dimensional Drawings

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 DIMENSIONAL DRAWINGS Rosemount 708 Direct Mount Dimensions are in inches (millimeters) Get other manuals https://www.bkmanuals.com...
  • Page 36: Ordering Information

    September 2012 ORDERING INFORMATION Table A-1. Rosemount 708 Acoustic Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
  • Page 37: Approved Manufacturing Locations

    RF spectrum. Nearly every country Compliance requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the rise of violating country directives or laws governing wireless device usage.
  • Page 38: Hazardous Locations Certificates

    Enclosure Type 4X / IP66/67 Special Conditions for Safe Use (X): 1. The Rosemount 708 Wireless Acoustic Transmitter shall only be used with the SmartPower Solutions, model number 701PGN green power module. 2. Potential Electrostatic charging Hazard – See Instructions.
  • Page 39 For use with SmartPower Solutions, model number 701PGN green power module only. 1180 Special Conditions for Safe Use (X): 1. The engineered polymer enclosure of the Rosemount 708 may constitute a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth. Standards:...
  • Page 40 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Figure B-1. Rosemount 708 FM Intrinsically Safe Installation Drawing Get other manuals https://www.bkmanuals.com...
  • Page 41: Effective Range

    Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Appendix C Recommended Practices Effective Range ........page C-1 All recommended practices should be followed to ensure highest data reliability.
  • Page 42 Reference Manual 00809-0100-4708, Rev AD Rosemount 708 September 2012 Get other manuals https://www.bkmanuals.com...
  • Page 43 Get other manuals https://www.bkmanuals.com...
  • Page 44 The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of the Emerson Process Management group of companies. HART is a registered trademark of the HART Communication Foundation.

Table of Contents