5.3 A
NALOG
Item
Loop Control Module
(LCM)
Loop Expander Module
(LEM)
5.4 A
NNUNCIATORS
Item
ACM32 Annunciator
ACM16AT Annunciator
SCS-8 Annunciator
LDM-32 Annunciator
LDM-R32 Annunciator
5.5 F
M
IELD
Item
AZM-8
Fan Controller (FAN-C)
Note:
Please note that the FAN-C module has been discontinued and will not be supplied for new installations.
When annunciators or field modules are powered from external power supplies, use a separate conductor to
connect the main power supply common terminal (-0V) to the remote power supplies common terminal (-0V).
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
A
DDRESSABLE
Description
Loop Controller for Loops 1,3,5,7,9
Loop Controller for Loops 2,4,6,8,10
Description
32 Red LED
16 x Pushbutton inputs
16 x Red LED
16 x Yellow LED
8 x 3 Position switches
8 x Red LED
8 x Yellow LED
8 x Green LED
1 x Fire Trip (A/C) Reset switch
1 x Fire Trip (A/C) Activated/Latched LED
32 x LED outputs (Open Collector)
32 x Relay outputs rated to 1A @ 30Vdc
ODULES
Description
8 x AZF inputs (4k7 EOL resistor)
4 x Programmable Relay Outputs
3 x Inputs (Opto-isolated, not monitored)
3 x Programmable Relay outputs
L
OOPS
System Capacity And Expandability
Notes
Max 5 per AFP-2800
Max 1 per AFP-2802
Max 5 per AFP-2800
Max 1 per AFP-2802
LEM "piggybacks"
onto LCM.
Notes
A maximum of 50
annunciators can be
connected to the
communications ring.
Notes
A maximum of 100
field modules can be
connected to the
communications ring.
Larger/external power
supplies and separate
feeds are required for
systems with a large
number of modules or
long cable runs.
The RS485 signal is
regenerated at each
field module.
15