Notifier AFP-2800 Operation, Installation & Programming Manual page 112

Intelligent, analogue addressable panel with non-proprietary programming tools
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

Appendix
8.7.1.3
M
AIN
SOCKET
PLUG
-
+
-
+
TERM 6
TERM 4
Note:
Terminate the shield at the outside of the FIP cabinet (ground). Where this is not possible, the shield must be
terminated to physical ground immediately adjacent to cable entry. Between Field modules, connect shields
together outside of their respective enclosures. Make sure that the shield is only grounded at the FIP and not
at the modules or annunciators. Do not ground both ends of the shield; one end should be left floating.
8.7.1.4
M
AIN
SOCKET
PWR A(+)
PWR A(-)
PWR B(+)
PWR B(-)
+AZ1
-AZ1
+AZ2
-AZ2
TERMINATION BOARD
8.7.1.5
M
AIN
+AZ1
-AZ1
+AZ2
-AZ2
TERMINATION BOARD
110
T
B
ERMINATION
OARD
-IN
+IN
SHIELD
-OUT
+OUT
T
B
ERMINATION
OARD
PLUG
T
B
ERMINATION
OARD
4700 Ohms
– C
ONNECTING
SHIELD
COMMS CABLE TO FIRST MODULE
COMMS CABLE FROM LAST MODULE
– C
ONNECTING
TO FIRST
MODULE IN
LOOP
+ 24V
- 24V
- 24V
+ 24V
FROM LAST
MODULE IN
LOOP
– C
ONNECTING
ALARM ZONE INPUT
UNUSED INPUT
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
RS485
24VDC
AZF'
1 & 2
S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-2802

Table of Contents