Page 4
Installing Row Ribbon Cables for CAB-B3, CAB-C3, and CAB-D3 Cabinets ..2-15 Installing Row Ribbon Cables for CAB-C3 and CAB-D3 Cabinets ....2-16 Installing Row Ribbon Cables for a CAB-400AA Cabinet .........2-17 Installing the CPU ....................2-18 Installing the CPU into a Chassis.................2-18 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 5
Measuring Total Wire Length for a Two-wire SLC ........2-43 Wire Requirements for a Four-Wire SLC ............2-45 Measuring Loop Resistance for a Four-Wire SLC ..........2-45 Measuring Total Wire Length for a Four-wire SLC........2-45 Style 6 Wiring Overview .................2-46 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 6
Installing Audio Amplifiers (AA-30/AA-100/AA-120) ........4-10 Installing an AA-30....................4-10 Overview......................4-10 Mounting an AA-30..................4-10 AA-30 Terminals and Connectors ..............4-11 Installing an AA-100/AA-120................4-12 Overview......................4-12 Mounting an AA-100/AA-120.................4-12 AA-100/AA-120 Terminals and Connectors ...........4-13 Installing a Backup Amplifier ................4-14 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 8
Wiring Diagram .....................5-5 Network Interface Board (NIB-96).................5-6 NIB-96 Overview....................5-6 NIB-96 Assembly....................5-6 NIB-96 SLC and EIA-485 Connections ..............5-7 Wiring Specifications.....................5-7 Using the XP Transponder with the AFP-300/AFP-400 ........5-8 XP Transponder Overview..................5-8 Wiring Diagram .....................5-8 Combination Fire/Security Applications..............5-9 Overview ........................5-9 General Operation ....................5-9 Installing a Security Tamper Switch ..............5-9...
Page 9
Overview......................A-15 Power Connections for LCD and ACS Annunciators........A-15 Power Connections for LCD-80s..............A-15 ACS and LDM Series EIA-485 Connection ............A-16 Connection Guidelines..................A-16 ACS and LDM Series EIA-485 Connections ..........A-16 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 10
How to Use Table G-2 ..................G-2 Calculating the Maximum Secondary Power Fire Alarm Current Draw ....G-4 Calculating the Battery Requirements ..............G-5 Calculating the Battery Capacity ................G-5 Calculating the Battery Size.................. G-5 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 11
NFPA 17 Dry Chemical Extinguishing Systems NFPA 17A Wet Chemical Extinguishing Systems NFPA 72-1993 Central Station Fire Alarm Systems (Automatic, Manual and Water- flow) Protected Premises Unit (requires Notifier UDACT). NFPA 72-1993 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
Page 12
AFP-300/AFP-400 Basic System Connections 50683 The AFM-16A Annunciator 15207 The AM2020/AFP1010 Manual 15088 Veri-Fire 400 Product Installation Document 50376 The UDACT Manual 50050
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 13
Table 1-1 Supplemental Documentation 'HVFULSWLRQ The AFP-300 and AFP-400 control panels are modular, intelligent fire alarm control panels (FACP) with an extensive list of powerful features. The CPU module, power supply module, mounting chassis, and cabinet combine to create a complete fire alarm control system with Notifier’s VIEW™...
The electrical limitations of the system power supply, including auxiliary power supplies used for notification appliances. The capacity of the Secondary Power Source (standby batteries). Refer to System Components, for descriptions of the various optional modules. Refer to Section 2, Installation for installation information. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 15
Introduction 6\VWHP 2YHUYLHZ $)36\VWHP'LDJUDP Figure 1-1 shows an AFP-300 system installed in a CAB-400AA with a voice alarm system and a full complement of installed devices )LJXUH $)3 6\VWHP 'LDJUDP AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
10,000 ft. per channel (NFPA Style 4) or 10,000 ft. total loop length (NFPA Style 6 and 7) Maximum loop current 250 mA (max short circuit) or 100 mA (normal) Maximum loop resistance 40 ohms (supervised and power-limited) Table 1-4 SLC Specifications AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
SRZHU UHTXLUHPHQWV UHIHU WR • Up to 1.25 A is available for powering four-wire smoke detectors. WKH SRZHU VXSSO\ FDOFXODWLRQ WDEOHV LQ $SSHQGL[ * For 24 VDC detectors, refer to the Device Compatibility Document for compatible detectors. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
The battery charger is current-limited and can recharge sealed lead-acid type batteries. 6HFRQGDU\ 3RZHU 6RXUFH The charger shuts off when the control panel is in alarm. %DWWHULHV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
System Components 6\VWHP 2YHUYLHZ 6\VWHP&RPSRQHQWV %DVLF(TXLSPHQW3DFNDJHV Basic Equipment packages for the AFP-300 and AFP-400 include the following: AFP-300 Basic Equipment Packages • BE-300AA – Base Equipment for use with the CAB-400AA mini cabinet. It is similar to the BE-300 but for use in CAB-400AA. Includes MPS-400RB and transformers.
The MPS-400 supplies a total of 6 A in alarm, used for the 036 UHTXLUHG following: (a) powering AFP-300/400 modules; (b) powering a variety of UL-listed 24 VDC notification appliances (refer to the Device Compatibility Document); and (c) providing up to 1.25 A of resettable power for four-wire smoke detectors. The MPS-400 contains an integral battery charger, four NAC/Releasing circuits, and four relay outputs (Alarm, Trouble, Supervisory, and Security).
Models of battery boxes are: • BB-17 battery box – for batteries up to 17 AH. • BB-55 battery box – for batteries up to 55 AH. 1-10 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Optional Devices 6\VWHP 2YHUYLHZ 2SWLRQDO'HYLFHV Table 1-7 contains a list of optional components that can be installed in an AFP-300 or AFP-400 system: Option Description UDACT A Universal Digital Alarm Communicator/Transmitter (UDACT) transmits system status to UL-listed Central Station Receivers over a public switched telephone network.
(Refer to Appendix C in the AFP-300/AFP-400 Programming Manual for details.) 'HWHFWRU'HVFULSWLRQV Table 1-8 contains a list of the intelligent detectors that you can use with an AFP-300 or AFP-400 system: Option Description BX-501 Standard U.S detector base...
BGX-101L) A dual action addressable manual pull station featuring a key-lock reset. The pull station includes an MMX-101 and responds to an address set with built-in rotary decimal switches. Table 1-9 Addressable Modules AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 1-13 www.PDF-Zoo.com...
End-of-Line Devices 6\VWHP 2YHUYLHZ (QGRI/LQH'HYLFHV Table 1-10 contains a list of the end-of-line devices that you can install in an AFP-300/ AFP-400 system: Option Description Notes System Sensor (SSD) A 47K End-Of-Line Resistor Supplied with MMX or A2143-00 (ELR) Assembly ELR used in the CMX modules.
Annunciator manuals. $QQXQFLDWRU&RQWURO0RGXOH5$&05 The ACM-8R provides the AFP-300 and AFP-400 with a mappable relay control module. ACM-8R relays can be selected for mapping anywhere in the system memory map (in groups of eight). Features of the ACM-8R include the following: •...
6\VWHP 2YHUYLHZ $QQXQFLDWRU&RQWURO6\VWHP$&6 The ACS series annunciator and control system provides the AFP-300 and AFP-400 with up to 32 remote annunciators, each with a capacity of 64 points. Table 1-11 contains brief descriptions of ACS annunciators. For detailed information, refer to the ACS Manual.
For installation instructions for these devices, refer to Section 2. /&''LVSOD\ The LCD-80 alphanumeric display module is an AFP-300/400 ancillary device that provides two modes of operation: Terminal, where it acts as a display repeater; and ACS, where it acts as an alphanumeric annunciator. The LCD-80 features the following: •...
CRM-4 or CRE-4 relay module. and the normally-closed ,&0 DQG &50 PRGXOHV contacts are rated for 10 A at 125 VAC and 30 VDC (resistive). Table 1-12 Notification Circuit and Control Relay Modules 1-18 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
The DCM-4 Dual Channel Module provides the system with the capability to select one of two types of audio sources for switching to a specified speaker circuit. The DCM-4 provides up to four circuits. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 1-19 www.PDF-Zoo.com...
The low-profile CHS-4L chassis mounts into a CAB-X3 cabinet. Use the CHS-4L chassis to mount AA-30 audio amplifiers, Audio Message Generators, Fire Fighters Telephones, or Audio Visual Power Supplies. )LJXUH &+6/ &KDVVLV 1-20 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
)LJXUH &$%$ 0RXQWLQJ 'LPHQVLRQV An optional TR-B3 trim ring is available for use with a B-size cabinet (24-1/8"W by &$%% 30-13/16"H). Replacement parts: DR-B3 door; SBB-B3 backbox. )LJXUH &$%% 0RXQWLQJ 'LPHQVLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 1-21 www.PDF-Zoo.com...
Page 34
)LJXUH &$%& 0RXQWLQJ 'LPHQVLRQV An optional TR-D3 trim ring is available for use with a D-size cabinet (24-1/8"W by
48-3/16"H). Replacement parts: DR-D3 door; SBB-D3 backbox. )LJXUH &$%' 0RXQWLQJ 'LPHQVLRQV 1-22 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 35
Cabinet Hardware 6\VWHP 2YHUYLHZ &$%$$&DELQHWV The CAB-400AA is a backbox and door that can contain a small AFP-300/AFP-400 &$%$$ 2YHUYLHZ system. (A small system supports up to twelve NACs and consists of a CPU and one option module, such as an ICM-4/ICE-4.) Modules mount to rails in the CAB-400AA, eliminating the need for optional chassis assemblies.
In addition, installers should be familiar with the following 6WDQGDUGV DQG &RGHV standards: • NEC Article 300 Wiring Methods. • NEC Article 760 Fire Protective Signaling Systems. • Applicable Local and State Building Codes. • Requirements of the Local Authority Having Jurisdiction. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
"Installing a 4XTM Module UZC-256, UDACT). (Remote Station Fire Alarm)" on page 2-22. "Installing a UZC-256 Module" on page 2-24. Install optional Voice Alarm System components. Section 4. Field-wire each module. "Field-Wiring the Modules" on page 2-25. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 39
The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This only applies to an unconfigured system.) Each AVPS-24 The yellow Trouble indicator comes on because batteries are not connected. Table 2-2 AC Power Checklist AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Mark the two holes, remove the backbox and drill the mounting holes. Mount the backbox, then install and tighten the remaining fasteners. When the location is dry and free of construction dust, reinstall the CPU board. Table 2-4 Mounting a Cabinet Backbox AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
3ODFLQJ DQ 036 RQWR D 6XSSRUW %UDFNHW Secure the bottom of the MPS-400 to the bottom cabinet support with the mounting screws as shown in Figure 2-10: 0RXQWLQJ VFUHZV )LJXUH 0RXQWLQJ DQ 036 LQWR D &$%; AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Tighten the mounting nuts until the module is secure. Figure 2-12 shows how to mount an AVPS-24 onto a CHS-4L chassis: &+6&+6/ $936 1XW DQG ORFNZDVKHU SODFHV )LJXUH 0RXQWLQJ DQ $936 3RZHU 6XSSO\ 2-10 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
)LJXUH 0RXQWLQJ DQ $50 WR D &+6 &KDVVLV Position the ARM-4 module over the existing standoffs on the chassis; then, fasten the ARM-4 module to the chassis with the two module retaining screws as shown in Figure 2-14. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-11 www.PDF-Zoo.com...
Page 48
Connect the other end of the ARM-4 cable to jumper JP5 on the CRM-4 or CRE-4 driving the ARM-4 module (Figure 2-15): $50 &DEOH 31 $50 &50 RU &5( )LJXUH &RQQHFWLQJ WKH $50 WR D &50&5( 2-12 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
CPU and the MPS series) to J2 on the MPS. Table 2-7 System Harness Connections Figure 2-16 contains a block diagram that shows system power connections between 6\VWHP 3RZHU the MPS-400 and AFP-300/AFP-400 system components: &RQQHFWLRQV Standard 3RZHU +DUQHVV Optional &38...
Figure 2-21: 0RGXOH VFUHZV SODFHV 6ORWV )LJXUH 6HFXULQJ D &38 WR D &KDVVLV Align the module screws with the thread-holes on the chassis and secure in place. 2-18 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
0RGXOH Install the four module support screws (removed earlier) through the back of the Expander Module and 0RGXOH VXSSRUW VFUHZ into the standoffs. Table 2-8 Installing an Expander Module 2-20 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Push the upper end of the module into the slots in the chassis. Secure the module to the chassis with the two module screws (Figure 2-24). 0RGXOH VFUHZ )LJXUH 6HFXULQJ D 0RGXOH WR D &+6 &KDVVLV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-21 www.PDF-Zoo.com...
Page 63
Positions E, F, G, and H are active only with the ICE-4 installed. You can also install a CRE-4 module on the ICM-4, connected as shown in Figure 2-36: ,&( PRGXOH ,&0 PRGXOH )LJXUH )LHOG:LULQJ DQ ,&( AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-27 www.PDF-Zoo.com...
Page 69
0.25 in. between power-limited and nonpower-limited wiring. For more information on power limiting, refer to Appendix F, UL Power-limited Wiring Requirements. Figure 2-46 shows the terminal connections to TB1 on the MPS-400: )LJXUH 036 7HUPLQDO 7% &RQQHFWLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-33 www.PDF-Zoo.com...
Page 70
5HOHDVLQJ &LUFXLWV circuit. For more information, refer to "Releasing Applications" on page 5-18 and the AFP-300/AFP-400 Programming Manual. Refer to the Notifier Device Compatibility Document, for a list of compatible releasing devices. The control panel provides a set of Form-C alarm and a set of 6WDQGDUG 5HOD\V Form-C trouble contacts rated for 2.0 A @ 30 VDC (resistive).
Page 71
XON/XOFF Character Set Standard S1. Zero Auto LF MENULOCK PAPER BIN 1 12/72" BIN 2 12/72" SINGLE 12/72" PUSH TRA 12/72" PULL TRA 12/72" PAP ROLL 12/72" PAPOPT Table 2-12 PRN-4 Setup Options AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-35 www.PDF-Zoo.com...
Page 72
Connect the cable between the CPU and the PRN-4 through an EIA-232 interface 1RWH 2XWSXWV DUH SRZHUOLPLWHG EXW DUH QRW as shown in Figure 2-50: VXSHUYLVHG 3OXJ WKH '% FRQQHFWRU LQWR WKH (,$ SRUW RI WKH SULQWHU351 351 &38 )LJXUH 5HPRWH 3ULQWHU &RQQHFWLRQV 2-36 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 73
Set the printer DIP switches SP1 and SP2 according to settings in Table 2-13: SP1 settings: SP2 settings DIP Switch SP1 DIP Switch SP2 SP1-1 SP2-1 SP1-2 SP2-2 SP1-3 SP2-3 SP1-4 SP2-4 SP1-5 SP2-5 SP1-6 SP2-6 SP1-7 SP2-7 Table 2-13 Keltron DIP Switch Settings AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-37 www.PDF-Zoo.com...
Page 75
BX-101L in an SLC. Wiring a BX-101L Addressable "SLC Wiring with a BX-101L Addressable Manual Pull Station" on Pull Station page 2-61, which covers wiring an Intelligent Detector in an SLC. Table 2-15 SLC Wiring Topics AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-39 www.PDF-Zoo.com...
Page 77
Alarm/Trouble indicates an alarm signal can be transmitted to the control panel during the abnormal condition. • SLC operation meeting Style 7 requirements isolates entire physical zones on the SLC from faults that occur within other areas of the SLC. Table 2-17 SLC Performance AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-41 www.PDF-Zoo.com...
Page 84
(labeled “Continuation of the SLC” in Figure 2-67) and all addressable devices on the isolated branch will report a trouble condition at the CPU. &RQWLQXDWLRQ RI WKH 6/& 6/& 77 DSSHG EUDQFK RII WKH 6/& )LJXUH :LULQJ DQ ,62; 2-48 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 85
The IDC provides the following services (do not mix): Fire Alarm Service. Automatic/Manual Waterflow Alarm Service with normally open contact devices. Sprinkler Supervision with normally open contact devices. Security Service. Maximum IDC wiring resistance is 20 ohms. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-49 www.PDF-Zoo.com...
Page 90
7HVWLQJ D &0; 0RGXOH Activate the test switch by placing a magnet over the CMX plastic cover. A test switch activation causes a short circuit indication on a Style B or Style D NAC. 2-54 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 91
Method 2 – An alternate power Figure 2-78 arrangement where you power the CMX (terminals 3 and 4) from one of the NACs on the MPS-400. Table 2-23 Applications for SLC Wiring with CMX Modules AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-55 www.PDF-Zoo.com...
Page 99
Return all circuits to their pre-test condition. Check that all yellow LEDs are off and the green AC POWER LED is on. Notify fire, central station and/or building personnel when you finish testing the system. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins. Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
9RLFH$ODUP6\VWHP 6HFWLRQ2YHUYLHZ This section contains instructions for installing and wiring modules that can be used in an AFP-300/AFP-400 voice alarm system. Table 4-1 contains the topics covered in Section 4. Section Covers the following topics... Page Installing an AMG Mounting an AMG/ATG Assembly...
Angle the bottom edge of &DSWLYH VFUHZ the module into the bottom slot of the CHS-4L. Secure the module to the CHS-4L with the captive &DSWLYH VFUHZ screws. )LJXUH ,QVWDOOLQJ DQ $0* 0RGXOH AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 103
Connector From AMG... AA... Low Level Audio Output to first P4-5 P3-5 amplifier P4-4 P3-4 Low Level Audio Output P4-2 P3-2 Return to last amplifier (optional) P4-1 P3-1 Table 4-2 AMG-1 Terminal Connections AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
P6 or P7; or wired to the audio P7 - ALERT amplifiers in other cabinets through P8. Power Harness Out Connecting to another power supply in the power supply chain. Table 4-7 Descriptions of ATG-2 Connections AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
SODFHV &+6/ ))7 RU ))76 )LJXUH 0RXQWLQJ WKH ))7))76 WR D &+6/ Mount TBP-1 dress panels on the FFT-7S as shown in Figure 4-7: 7%3 'UHVV 3DQHOV )LJXUH ))76 ZLWK 'UHVV 3DQHOV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 109
Connect to plug P6 on the AMG or plug P5 on the ATG-2. control harness (75097) No connection Two-wire/four- Set the control panel for four-wire operation: wire selector 1) Remove the switch cover. switch 2) Set SW1 for four-wire operation. Table 4-8 FFT-7/FFT-7S Terminals and Connections AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Swing the assembly into the chassis. $$ &+6/ Secure the AA-30 to the chassis with the washers :DVKHU DQG UHWDLQLQJ and retaining nuts. QXW SODFHV )LJXUH 0RXQWLQJ DQ $$ LQWR D &+6/ &KDVVLV 4-10 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
9RLFH $ODUP 6\VWHP 9RLFH$ODUP0RGXOHV 2YHUYLHZ Voice alarm modules for the AFP-300/AFP-400 feature removable terminal blocks that simplify installation and servicing of the control panel. These modules include the Voice Control Module (VCM-4), the Voice Control Expander (VCE-4), and the Dual Channel Module (DCM-4).
Page 120
Audio Signal Wiring Using a Backup Amplifier Figure 4-27 on page 4-24 Figure 4-28 on page 4-24 CPU-400 Trouble Bus Connections Figure 4-29 on page 4-25 Figure 4-30 on page 4-25 Table 4-15 Voice System Configurations 4-20 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 121
)LJXUH 6\VWHP &RQILJXUDWLRQ ² ,QWHUQDO 3RZHU 'LVWULEXWLRQ %ORFN 'LDJUDP Figure 4-22 shows a simplified block diagram for distributing internal power within a voice system: $0* RU 036 $0* ))7 &38 $7* )LJXUH 'LVWULEXWLRQ RI ,QWHUQDO 3RZHU %ORFN 'LDJUDP AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 4-21 www.PDF-Zoo.com...
Page 122
)LJXUH &38 (,$ &RQQHFWLRQV %ORFN 'LDJUDP Figure 4-24 shows a simplified block diagram EIA-485 connections between the CPU and EIA-485 connections: 2SWLRQDO 2SWLRQDO &38 $0* $QQXQFLDWRU $QQXQFLDWRU )LJXUH %ORFN 'LDJUDP IRU 'LVWULEXWLRQ RI (,$ 4-22 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 135
Step Action Remove battery power, then remove AC power from the AFP-300/AFP-400. Remove the dress panel covering the AMG-1. Remove the four screws that hold the AMG1 dress panel to the component board as shown below.
Page 136
Figure 4-42 shows a block diagram of a remote annunciator powered from a local power supply: &38 5HPRWH $QQXQFLDWRU 036 036 0DLQ &DELQHW 5HPRWH &DELQHW )LJXUH 5HPRWH $QQXQFLDWRU 3RZHUHG IURP D /RFDO 3RZHU 6XSSO\ 4-36 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 137
Daisy-chain the secondary side of the ACT-1 (low-level audio) up to a maximum of eight amplifiers. Draw additional low level audio risers (isolated from the main riser) from P4 on an audio amplifier. 7DEOH &RQQHFWLQJ DQ $&7 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 4-37 www.PDF-Zoo.com...
• a Releasing Device to the MPS-400. • a Releasing Device to an ICM-4/ICE-4 Module. • a Releasing Device to a CMX Module. • an N-ARA-10 Agent Release-Abort Station. • a Combination Waterflow/Supervisory Valve Monitor. 7DEOH $)3$)3 $SSOLFDWLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
General Supervisory signals, and will receive Acknowledge, Silence, and Reset commands automatically from the AM2020/AFP1010. To transmit zone alarm and zone trouble information, program the AFP-300/AFP-400 points to software zones 1 through 99. For information on installing and programming the Receiving unit, refer to the AM2020/AFP1010 and NIB-96 manuals.
Typically, NIB-96 modules are physically located in each slave control panel, which can contain 8 to 96 input/output points. This section contains board and wiring information for connecting a NIB-96 to an AFP-300/AFP-400 control panel. Circuit Requirements...
Page 145
Supervised and power-limited ±5 volts peak-to-peak Maximum wiring distance: 6000 feet at 14 AWG Maximum circuit resistance: 40 ohms Characteristic impedance of wiring: 120 ohms Transmission rate: 2400 baud 7DEOH 1,% :LULQJ 6SHFLILFDWLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
CPU through an SLC loop. If the CPU fails or loses power, the XP can operate in a degraded stand-alone mode. To the AFP-300/AFP-400, XP Transponder circuits appear as individual addressable monitor or control modules. For more information, refer to the XP Transponder manual.
For bypass of security zones, use the DISABLE routine (covered in the Status Change section of the AFP-300/AFP-400 Operations Manual) for Security ALA type devices. ,QVWDOOLQJD6HFXULW\7DPSHU6ZLWFK Wire the cabinet with a security tamper switch kit (Figure 5-8). CAB-400AA cabinets require tamper switch model STS-200;...
Page 148
Select the address of the monitor module(s) to be used for security; and 1RWH )RU GHWDLOHG LQVWUXFWLRQ RQ SURJUDPPLQJ W\SH FRGHV Set the type code to Security ALA. UHIHU WR WKH $)3$)3 3URJUDPPLQJ 0DQXDO 5-10 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Female DB-9 connector for programming from an IBM-compatible computer. Connection EIA-485 All connections are power-limited and supervised. See Figure 5-12 on page 5-13 for Connection terminal assignment. 7DEOH 'HVFULSWLRQV RI 8=& &RPSRQHQWV 5-12 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
The control panel supports a maximum of ten releasing areas. You can divide the releasing circuits among the MPS-400 releasing outputs, the ICM-4, ICE-4, and CMX modules. For more information, refer to the AFP-300/AFP-400 Programming manual. (
Table 5-10 contains references to wiring diagrams for releasing applications: To connect...
Page 157
For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the AFP-300/AFP-400 Programming Manual for instructions on setting the Soak Timer. In applications not requiring power-limited circuits – a) End-of-Line devices (PN REL-2.2K) are not required;...
Page 158
For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the AFP-300/AFP-400 Programming Manual for instructions on setting the Soak Timer. In applications not requiring power-limited circuits – a) End-of-Line devices (PN REL-4.7K) are not required;...
Page 159
Make sure to keep total system current within the limits of the power supply. You can power the CMX from the MPS-400 or any UL-listed 24 VDC power-limited power supply for Fire Protective Signaling. For more information, refer to the Notifier Compatibility Document.
Page 160
Program the module or NAC for type code “Rel Ckt ULC.” For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the AFP-300/ AFP-400 Programming Manual for instructions on setting the Soak Timer.
Page 161
6XSHUYLVHG DQG 3RZHUOLPLWHG The following list includes requirements for the Combination Waterflow/Supervisory Valve Monitor circuit. (Refer to the AFP-300/AFP-400 Programming Manual for details on programming a Monitor Module.) The Waterflow Alarm Switch must connect to the Monitor Module initiating input before the In Line Resistor.
• Tables necessary for configuring the annunciator display; and • Typical annunciator wiring diagrams. Note that Appendix A contains information specific to the AFP-300/AFP-400 only. For complete annunciator installation information, refer to the respective annunciator manual. $QQXQFLDWRU,QWHUIDFHV The control panel provides Terminal Mode (LCD-80) and ACS Mode Interfaces that provide high speed, two-way communication link to multiple annunciators.
When using an LCD-80 in ACS mode for system annunciation, you must assign ACS Selection Group 1 to the LCD-80’s start address. (For instructions on assigning ACS Selection Groups, refer to the AFP-300/AFP-400 Programming Manual.) LCD-80s used in ACS mode for point annunciation can use other ACS Selection Groups for their start address.
Page 165
Input Zone 54 Active Zone 54 Trouble Not Used Input Zone 55 Active Zone 55 Trouble Not Used Input Zone 56 Active Zone 56 Trouble Not Used 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 168
Input or Output Module 263 Active Module 263 Trouble Controls Output Module AFP-400 only Input or Output Module 264 Active Module 264 Trouble Controls Output Module AFP-400 only 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 169
Input or Output Module 295 Active Module 295 Trouble Controls Output Module AFP-400 only Input or Output Module 296 Active Module 296 Trouble Controls Output Module AFP-400 only 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 170
Input Detector 162 Alarm Detector 162 Trouble Not Used Input Detector 163 Alarm Detector 163 Trouble Not Used Input Detector 164 Alarm Detector 164 Trouble Not Used 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 171
Input Detector 262 Alarm Detector 262 Trouble Not Used Input Detector 263 Alarm Detector 263 Trouble Not Used Input Detector 264 Alarm Detector 264 Trouble Not Used 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 172
Not Used AFP-400 only Input Detector 295 Alarm Detector 295 Trouble Not Used AFP-400 only Input Detector 296 Alarm Detector 296 Trouble Not Used AFP-400 only 7DEOH $ $&6 $QQXQFLDWRU 6HOHFWLRQ *URXS A-10 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
TB3 on the CPU. ACS and LDM Series EIA-485 Connecting an ACS series annunciator, A-16 Connection including the LDM-80), to TB4 on the CPU using an EIA-485 circuit. 7DEOH $ $QQXQFLDWRU 7RSLFV A-12 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 181
$SSOLDQFH &LUFXLWV \RX FDQ following: Use twisted-pair shielded wire for any wiring entering or exiting the UHGXFH SUREOHPV E\ H[FOXVLYHO\ AFP-300/AFP-400 cabinet that is not enclosed in conduit. XVLQJ HOHFWURQLF VRXQGHUV VXFK DV WKH 0$66 6HULHV LQVWHDG RI PRUH HOHFWURQLFDOO\ QRLV\...
Page 183
$SSHQGL[&&RPSDWLEOH(TXLSPHQW This document lists Notifier and System Sensor equipment that is compatible with the control panel. Also, refer to the Device Compatibility Document, 15378 for compatible equipment. 1RWLILHU&RPSDWLEOH(TXLSPHQW 4XTM Transmitter Module CRM-4 Control Relay Module AA-30 30-Watt Audio Amplifier CRT-2 Video Display Monitor with Keyboard...
Page 186
RQOLQH KHOS responsible service personnel in attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72-1993. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Read Status, Alter Status, and Control Functions (Table E-1). Functions: Passwords: User-defined password for Alter Status functions. Requirements: The terminal must be mounted in a UL-864 listed enclosure, a Notifier Rack-51, Rack-67, or positioned to provide equivalent protection against unauthorized use. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 188
• Clear the verification counter of all detectors. • Clear the entire history buffer. • Set the AWACS alert and action levels. Control Functions • Acknowledge • Alarm Silence • System Reset • Alarm Activate 7DEOH ( /RF0 )XQFWLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
• Display a list of all programmed points in the system. • Step through the history buffer event by event. • Display the entire history buffer. Alter Status Control Functions 7DEOH ( 5HP7 )XQFWLRQV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Press the Read Status function key – F1. The control panel displays the Read Status menu options: Press 5G 3RLQW 5G $OP7EO $OO 3RLQWV +LVW6WHS $OO $OD+LVW6WHS $O From the Read Status menu, you can select options 1-5. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 192
35,17 (1' The semicolon, a control character in networking applications, separates the hour and minute of events displayed from history. If events display as they occur, a colon separates the hour and minute. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Press 11111 The Alter Status Options menu appears: 'LVDEOH $ODUP3UHDODUP &OHDU 9HULILFDWLRQ &OHDU +LVWRU\ $OHUW$FWLRQ From the Alter Status Options menu, you can select options 1-5. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Set Action/Alert lets you set the Pre-Alarm for Alert or Action. For example, Change Pre-Alarm from “Alert” to “Action” as follows: Press 6HW 3UHDODUP $OHUW12$FWLRQ<(6 7\SH 1 RU < WKHQ (QWHU 67$786 &+$1*( &KDQJH $OHUW$FWLRQ $ :HG Press 3UHDODUP QRZ VHW IRU $&7,21 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Figure F-1 shows a typical wiring diagram for the control panel. The first two rows show rows of modules configured with at least a 0.25 inch separation between power-limited and nonpower-limited wiring. 3RZHUOLPLWHG &LUFXLWV 1RQSRZHUOLPLWHG 1RQSRZHUOLPLWHG &LUFXLWV &LUFXLWV )LJXUH ) 7\SLFDO :LULQJ IRU 8/ 3RZHUOLPLWHG :LULQJ 5HTXLUHPHQWV AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 201
The requirements for non-fire alarm and fire alarm current loads cannot exceed the capabilities of the MPS-400 listed below: • 3 A at 24 VDC during Standby; and • 6 A at 24 VDC during Alarm. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
AC power loss.) The non-fire alarm current is required to complete the standby battery calculations. After summing all current draws, insert the total in Table G-3. AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 www.PDF-Zoo.com...
Page 207
Limited anty TIFIER TIFIER ® ® ® ® ® NOTIFIER TIFIER TIFIER warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation ®...