AM2020/AFP1010 with SIB-NET Document 15094 11/20/95 Rev: P/N 15094: C ECN 95 -210 www.PDF-Zoo.com...
Page 2
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to Like all solid state electronic devices, this system may operate this fire alarm control panel. Disconnect all sources of power before erratically or can be damaged when subjected to lightning induced servicing.
Table of Contents Section 1 Installing the Serial Interface Board for the AM2020/AFP1010 ............4 Section 1.1 Introduction ........................4 Table 1-1 SIB-NET Related Documentation .................. 5 Figure 1-1 NROM-2.0/2.5 with 1 SIB-NET Chip ................6 Section 1.2 Mounting the Interconnect Chassis Assemblies ............. 6 Figure 1-2 Mounting the ICA-4L and System Boards ..............
Media Interface Board (MIB), the SIB can communicate with . This allows the AM2020/AFP1010 to transmit alarm and trouble events through the network to other network nodes for display and recording. Also, the network allows the NRT/INA to perform reset, acknowledge, and signal silence functions at the AM2020/AFP1010.
Page 5
Title Number AM2020/AFP1010 Fire Alarm Control Panel 50119/15088 The LCD-80 Liquid Crystal Display 15037 The Network Reporting Terminal (NRT) 15090 The Intelligent Network Annunciator (INA) 15092 Network Serial Interface Board (SIB-NET) 15094 The UZC-256 Universal Zone Coder Installation 15216 CCM-1 Product Installation Document...
Figure 1-1: NROM-2.0/2.5 with 1 SIB-NET Chip Section 1.2: Mounting the Interconnect Chassis Assemblies The AM2020/AFP1010 system can use one to three Interconnect Chassis Assemblies (ICA-4/ICA-4L), depend- ing on the specific installation requirements (the AFP1010 requires only one). If using more than one ICA-4/ ICA-4L, interconnect each ICA-4/ICA-4L before connection to the backbox by mating the plug connector on one chassis to the socket connector on the other (no cable required).
Page 7
Older power cable (part number 71030) Warning! The ICA-4L chassis includes a 16th pin (see Figure C Figures A and B) for connection to the system boards (CPU, SIB, LIB, and so on) which is not used at this time. NOTE: There is no extra pin when using a SIB-NET.
Page 8
When connecting two ICA-4L chassis using an expansion power cable (part number 75142), there will be an extra pin on one chassis and an extra receptacle on the other. Both the extra pin and the receptacle should be in the front, facing the cabinet door (see Figure 1-3). •...
The SIB-NET mounts on the ICA-4L chassis. The AM2020/AFP1010 system connects to and interfaces to the network through the MIB and the SIB-NET. The MIB mounts onto the SIB-NET. The chassis is compatible with the ICA-4. For more information on the ICA-4L, refer to the installation section in the AM2020/AFP1010 Manual.
Page 10
To ICA-4L EIA-485 Reference Earth Ground EIA-485 (+) EIA-485 (-) EIA-485 (+) Terminals 1-4: Provide wiring for one PRN printer to EIA-485 (-) this unsupervised circuit. EIA-232 Reference Terminals 5-8: Provide connection to the Keltron Transmit to Printer VS4095/5 printer or any UL EDP-listed printer. Connec- EIA-232 Reference tion is not supervised.
CRTs with installer-provided cables (AUX on first CRT to EIA port on second CRT, and so on). Multiple Terminals The AM2020/AFP1010 supports up to 25 terminals installed on the EIA-232 circuit of the Serial Interface Board. Each CRT is shipped from the factory with a keyboard, used for programming the FACP. The keyboard can only be used on the first CRT installed in the chain.
Page 12
Refer to the EIA- 232E standard. CRT with Keyboard One maximum – the CRT-1 must be the first in a chain and must be in the same room as the AM2020/AFP1010. The CRT-2 can be located remotely. SIB-NET (Connector P3) EIA-232 Reference...
Printer Configuration Refer to the documentation supplied with the PRN-4 for instructions on the printer's menu con- The AM2020/AFP1010 can employ PRN-4 remote trols. Set the printer's options as follows: printers. PRN-4 remote printers provide hard-copy printout of all status changes within the system, and...
Page 14
Keltron Printer Model No. VS4095/5 (Refer to note 4 below.) SIB-NET 50 feet max (typical) Wiring distance limited by cable capacitance. Refer to the EIA-232E standard. SIB-NET Connector P3 EIA-232 Reference Twisted-pair Transmit to Printer EIA-232 Reference Twisted-pair Ready/Busy from Printer Plug this DB-25 connector into the EIA-232 port of the printer.
Page 15
The EIA-485 Reference (P5-1) for the SIB-NET must be connected to any ACS device which is not within the same cabinet or is not powered by the SIB-NET AM2020/AFP1010 power supply. Connect P5-1 of the SIB- NET to: • ACM-16AT at TB1-4 •...
Appendix A: Circuit/Device Ratings Distance Circuit Type Circuit Functions Wire Requirements Typical Wire Type (feet) Twisted-shielded pair, 12 to 18 10,000 Belden 9586 (12 AWG) West Penn 999 Connects to Intelligent and LIB-200 AWG, 40 ohms max per length of 8,000 Belden 9581 (14 AWG) West Penn 995 Addressable Modules, and...
Municipal Box Trip device and an Uninterruptable Power Supply in the nominal). (10 ohms max. loop resistance. Trip A77-716 power supervision relay. AM2020/AFP1010 Manual. current = 250 mA. Municipal Box Circuit Local Energy Municipal Box connection. XP Transponder XPC-8 module with Supervised and power-limited.
Page 18
Type of Circuit Devices/Ratings Circuit Ratings Connections CMX Control Module fed from an MPS-24A, Operating voltage supplied dependent on NFPA Style Y Activated Polarity CMX MPS-24B, AVPS-24, or other 24 VDC the signal power source employed. Terminal 6 (+), 7 (-) Notification Appliance power supplies listed for Fire Protective ELR=47K, 1/2 watt, Part #47K (N-ELR) in...
Page 19
Type of Circuit Devices/Ratings Circuit Ratings Connections 24 VDC (nominal), 1-Vrms max. 800 Hz to 2800 FFT-7/FFT-7S Connector P3 Term. 3 (+) and 2 (-) Hz. Seven (7) telephone handsets active at one to XPC-8 Connector P3.2 (+), P3.1 (-), and/or time max including Master Telephone.
Page 20
NFPA Style D (4 zones on XPM-8 P2):. stations, heat detectors, supervisory or max loop resistance. Supervised and waterflow switches, and 4-wire smoke power-limited (50 uA). See Notifier Device detectors. Compatibility Document, 15378, for a list of compatible 2-wire detectors.
Page 21
® For products not under NOTIFIER manufacturing date-stamp control, the warranty is eighteen (18) months from date of original purchase by NOTIFIER ® 's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.