Service Menu - Log Off - Notifier AFP-2800 Operation, Installation & Programming Manual

Intelligent, analogue addressable panel with non-proprietary programming tools
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

Panel Operation
6.3.9.5
S
ERVICE
This page displays network parameters that can be toggled.
NETWORK CONFIGURATION
DAY MODE
20 JULY 2002 14:44:37
SELECT A FUNCTION:
NETWORK BELL ISOLATE BROADCAST IS DISABLED
ACKN OF NETWORK FAULTS IS DISABLED
CHANNEL-A THRESHOLD ON NCM IS HI
CHANNEL-B THRESHOLD ON NCM IS HI
NCM FIELD WIRING STYLE IS CLOSED (STYLE 7)
...........................................
. WARNING!! CHANGING NETWORK OPTIONS WILL .
. MOMENTARILY REMOVE NODE FROM NETWORK
. UNTIL RE-INITIALISATION IS COMPLETE
...........................................
UP
DOWN
Actions:
 Use the UP and DOWN buttons to scroll through options and then use the TOGGLE button to select the
toggle the highlighted option. Changes are instant.
Explanation of Network Options:
Item
Network Bell Isolate
broadcast is disabled /
enabled
Acknowledge of network
faults is disabled /
enabled
Channel A Threshold is
High / Low
Channel B Threshold is
High / Low
NCM Field Wiring Style is
Closed / Auto-detect
6
.
3
.
1
0
S
6
.
3
.
1
0
S
E
R
V
E
R
V
This option on the service menu allows the current user logged onto the system to log off and return the system
back to level 0 access.
Failure to manually log off the system will result in the system automatically logging the user off after 5 minutes of
no button presses, to prevent the system remaining accessible after the technician has finished.
84
M
– N
ENU
ETWORK
A = 0
F = 0
I = 0
N = 1
.
.
TOGGLE
MENU
Description
This option allows you to broadcast a 'Bell Isolate' or a 'Warning System Isolate'
to the entire network from this panel. Usually enabled on "Master" FIP.
This option allows you to acknowledge all faults on the network with a single
ACK from this panel. Usually enabled on "Master" FIP.
Default value is high. Low threshold should only be used for long network cable
runs – refer to notifier network manual for more details.
Default value is high. Low threshold should only be used for long network cable
runs – refer to notifier network manual for more details.
Default is Closed (style 7) which forces the NCM to monitor both channel A & B
for communication loss. Auto detect will only monitor the channel(s) that have
"seen" other nodes (received data from other nodes).
M
M
I
C
E
E
N
U
L
O
G
I
C
E
E
N
U
L
O
G
– O
PTIONS
O
F
F
O
F
F
AFP-2800/2802 Manual – P/N 11249 11-Mar-08