Notifier AFP-2800 Operation, Installation & Programming Manual page 69

Intelligent, analogue addressable panel with non-proprietary programming tools
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

6.3.6.8
S
ERVICE
From this menu, the operator is able to perform alarm and fault tests on individual AZFs, operate a single digital
output point, perform a manual battery capacity test or perform a 'walk' test.
TEST MENU
DAY MODE
20 JULY 2002 14:44:37
USE UP/DOWN BUTTONS TO SELECT A FUNCTION
1) AZF ...... ALARM/FAULT CONVENTIONAL ZONE
2) ALARM .... ALARM TEST AN ANALOG INPUT
3) FAULT .... FAULT TEST AN ANALOG DEVICE
4) DOUT ..... TEST AN OUTPUT LED OR RELAY
5) BATTERY .. TEST THE BATTERIES
6) WALK ..... WALK TES ANALOG & CONV ZONES
UP
DOWN
Selection
Action required
1
Will take you to the AZF List – Where you can select an AZF from the AZF list as per page 40
and then press the TEST button to enter AZF Test Mode.
2
Perform an alarm test on an Analog addressable point. You will be prompted for loop number
and detector or module number.
3
Perform a fault test on an Analog addressable point. You will be prompted for loop number and
detector or module number.
4
Will take you to the Digital Output List – Where you can select an output from the DOUT list as
per page 41 and then press the TEST button to enter DOUT Test Mode.
5
Will perform a battery capacity test which will last 15 seconds (Not available in NZ mode). Note
that in NZ mode a battery fault on the PSI will latch on for up to 1 hour.
6
Will take you to the 'Walk Test Output Target List' where you can select an output for the Walk
Test. This output will activate for 2 seconds whenever a device is tested during the walk test.
You will then be asked to select the Group Zone or Loop you wish to test. You are then able to
remove individual devices from the walk test if you wish, or simply start the walk test.
Throughout the duration of the Walk Test, the 'FAULT', 'EXT BELL ISOLATE' and "WARNING
SYSTEM ISOLATE" front panel LEDs will pulse on and off.
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
M
– T
ENU
EST
A = 0
F = 0
I = 0
N = 1
SELECT
MENU
Actions:
Use the UP and DOWN buttons to scroll
through options and then use the SELECT
button to select the highlighted option
(or button 1 to 6 from the numeric keypad)
Press the MENU button to return to the
Service Menu screen.
Panel Operation
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-2802

Table of Contents