Fault Codes - Notifier AFP-2800 Operation, Installation & Programming Manual

Intelligent, analogue addressable panel with non-proprietary programming tools
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

8
.
6
.
6
F
8
.
6
.
6
F
A
A
U
U
L
L
These codes apply to Analog devices and are added to the history log as well as being displayed in the Fault List
when the fault occurs.
Actual Fault
Code Displayed
No Response
FAULT (F01)
Mismatched
FAULT (F02)
Hardware Type
Devices At Same
FAULT (F03)
Address
Incorrect Response
FAULT (F04)
Open Circuit
FAULT (F05)
Short Circuit
FAULT (F06)
Low Threshold
FAULT (F07)
Maintenance Alert
FAULT (F08)
Maintenance Urgent
FAULT (F09)
Verify Count Over 20
FAULT (F010)
Detector Failed Test
FAULT (F011)
Security Tamper
FAULT (F012)
Low Temperature
FAULT (F013)
Ground Fault
FAULT (F014)
Charger Fault
FAULT (F015)
Battery Low
FAULT (F016)
Battery High
FAULT (F017)
General Trouble
FAULT (F018)
Missing Address
FAULT (F019)
AC Fail
FAULT (F020)
Module External
FAULT (F021)
Power Loss
Wrong OEM Device
FAULT (F022)
Type
RFX Communication
FAULT (F023)
Loss
Beam Blocked
FAULT (F024)
Alignment Mode
FAULT (F025)
Device Disabled
FAULT (F026)
Zone Disabled
FAULT (F027)
Initialisation Mode
FAULT (F028)
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
C
C
T
T
O
O
D
D
E
E
S
S
Possible causes
The device in fault is not communicating with the LCM. This fault
can occur if the device is not physically connected, damaged or
set at wrong address.
The actual device type is different to the programmed type. This
fault would occur if an incorrect device type is used such as a heat
detector instead of a photo optical detector.
Two devices have the same address on the loop.
The device has returned an incorrect response. This fault can
occur if the device is faulty or the loop wiring is substandard. If the
resistance of the entire loop wire exceeds 50 ohms, this fault will
be observed intermittently.
An Analog module does not have the End Of Line resistor
connected or an incorrect value of EOL is used.
There is a short circuit on the output terminals of a Analog relay
module.
A low threshold fault indicates a faulty detector which needs to be
replaced.
Analog detector needs cleaning.
Analog detector needs cleaning urgently. Once the detector is in
maintenance urgent fault it will no longer provide reliable detection
of fire.
Not used on AFP-2800/2802
LCM performs a test on each detector every 2 – 3 hours. This
fault can occur if the device is faulty or the loop wiring is
substandard. If the resistance of the entire loop wire exceeds 50
ohms, this fault will be observed intermittently.
Not used on AFP-2800/2802
Not used on AFP-2800/2802
Less than 50kohms resistance to ground. The Ground Fault LED
on the affected LCM will be ON (refer to page 114)
Not used on AFP-2800/2802
Not used on AFP-2800/2802
Not used on AFP-2800/2802
General fault code that LCM uses when it can not detect the
actual problem with the device. This fault can occur if the device is
faulty or the loop wiring is substandard. If the resistance of the
entire loop wire exceeds 50 ohms, this fault will be observed
intermittently.
Not used on AFP-2800/2802
Not used on AFP-2800/2802
24 volt power is not connected to the Analog module.
(Conventional Zone and Control modules)
The device on the loop is using the wrong communication
protocol. Replace the device with a version that has compatible
protocol with the panel.
Not used on AFP-2800/2802
Beam Detector Fault - Beam path blocked
Beam Detector Fault - Detector in alignment mode
Not used on AFP-2800/2802
Not used on AFP-2800/2802
Beam Detector Fault - Detector initialising