System points will be displayed and can be referred to as follows:
Description
On Board AZF's
AZF #1
AZF #2
On Board Relays
Relay 1 to 8 on FIM
Distributed Field Modules
AZF
Din
Dout
Annunciator
Inputs
Outputs
Analog Addressable Devices
Detectors
Modules
Virtual Points
Network Points
Expansion Relays
System Parameters
Common Alarm
Common Fault
Common Isolate
Battery Fault
Charger Fault
Mains On
Ext. Bell Isolated
Warning System Isolated
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
Syntax
Comments
2 AZF's on termination Board
0.1.Z1
Ring 0 Module 1, zone 1
0.1.Z2
Ring 0 Module 1, zone 2
8 Relays on termination Board
0.4.O1 to 0.4.O8
Ring 0 Module 4, output 1
Ring 0 Module 4, output 8
Up to 100 modules
1.1.Z1
8 AZF points per AZM8module
1.1.I1
3 Din Per Fan Control Module
1.1.O1
4 Dout Per AZM-8
3 Dout Per Fan Control Module
Up to 50 Annunciators
1.101.I1
16 Din per 16AT, 24 Din Per SCS-8
1.101.O1
32 Dout Per 16AT, 24 Dout Per SCS-8, 32
Dout Per ACM32A
Up to 10 Loops
L1D1
159 Detectors Per Loop
L1M1
159 Modules Per Loop
VPn
n can range up to 1000
NPn
n can range up to 1000
XRn
n can range up to 64
CA
CF
CI
BF
CL
MO
BI
WI
Panel Operation
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-2802