8.7.1.1
POWER SUPPLY CONNECTIONS - PS243 & PS249
8.7.1.2
P
OWER
The following settings are used when connecting a NPS power supply to an IFS-724 FIM using the ribbon cable:
1. The CPU must have V5.02 or above firmware installed.
2. Set the bottom dipswitch on mode dipswitch U25 (on the back of the CPU) to the on position. Note that the
dipswitch can be marked 1 or 4. Always set the dipswitch closest to the upload/download port.
3. J6 on IFS-724 FIM board must be fitted.
Refer to Power
Supply Interface
(PSI) Manual for
more information
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
IFS-704/714/724 TERMINATION BOARD
S
C
UPPLY
ONNECTIONS
Fit Link at J6
NI-2012
Power Supply
Interface (PSI)
NI-2012 (PSI) Dipswitch Settings:
Normal operation:
All off
NZ Operation:
1 on, all others off
Manual mode:
2 on, all others off
TERM 2
- NPS-2/5/11
IFS-724 FIM
Termination Board
Appendix
109

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-2802

Table of Contents